User manual

GMC-I Messtechnik GmbH 37
Stop Sequence at Current Address
(status: RUN

HOLD)
Functions
! A running SEQUENCE can be suspended for an indefinite period
of time.
Uset, Iset and Sset retain the values specified in the current
memory location. Selected dwell time Tset of the current
memory location is not taken into consideration.
The output retains its switching status (output On or Off).
•The SEQUENCE can be resumed (cont) at the next memory
location, or ended at the current address <CE/LOCAL> or the stop
address (stop), or restarted (go).
In addition, step-by-step control can be started at the next
address (Step) or at the start address (Start) as well.
Procedure:
With running SEQUENCE,
– press the <ENTER> key
or
– press the <FUNCTION> key and then browse with the
<> key, the <> or the <FUNCTION> key
until SEq hold appears
and execute the command with the <ENTER> key.
! The command is executed when the key is released.
! The SEQUENCE stops at the current address.
! The LOCKED/SEQ LED blinks slowly in the HOLD status.
Resuming the Sequence from the HOLD Status
(status: HOLD RUN)
Functions
! A suspended SEQUENCE can be resumed at any time.
The output retains its switching status (output On or Off).
The selected dwell time of the of the exited memory location is
not taken into consideration.
! The sequence is now resumed starting with the next address,
and the values stored to the respective memory location (Uset,
Iset, tdef/tset and SSEt) are read out to the power and signal
outputs.
! In the case of very long dwell times, you can advance
prematurely to the next memory location by pressing the
<ENTER> key twice (status: RUN HOLD RUN).
Procedure:
With suspended SEQUENCE,
– press the <ENTER> key
or
– press the <FUNCTION> key and then browse with the
<> key, the <> or the <FUNCTION> key
until SEq cont appears
and execute the command with the <ENTER> key.
! The command is executed when the key is released.
! The SEQUENCE is resumed starting with the next memory
location.
! The LOCKED/SEQ LED blinks rapidly in the run status.
End the Sequence at the Stop Address (status: HOLD

RDY)
Functions
! A suspended SEQUENCE can be ended at any time by
executing the stop address.
If the memory location assigned to the stop address is empty,
the Uset, Iset and Sset values from the hold address are
retained. If the memory location assigned to the stop address
is not empty, Uset and Iset are changed to the corresponding
values. Selected dwell time Tset of the of the current memory
location is not taken into consideration.
The output status is determined by the content of the stop
address. The output retains its switching status (output On or
Off) if the memory location assigned to the stop address is not
empty. The output is switched to the off status if the memory
location assigned to the stop address is empty.
Procedure:
With suspended SEQUENCE,
– press the <FUNCTION> key and then browse with the
<> key, the <> or the <FUNCTION> key
until SEq stop appears
and execute the command with the <ENTER> key.
! The SEQUENCE is ended and the output status is determined
by the content of the stop address.
! The LOCKED/SEQ LED does not blink in the RDY status.
End the Sequence at the Current Address (status: HOLD

RDY)
Functions
! A suspended SEQUENCE can be ended at the current address
at any time.
Uset, Iset and Sset retain the values specified in the current
memory location. Selected dwell time Tset of the of the
current memory location is not taken into consideration.
The output retains its switching status (output On or Off).
Procedure:
With suspended SEQUENCE,
– press the <CE/LOCAL> key.
! The SEQUENCE is ended and the output status is determined
by the content of the current address.
! The LOCKED/SEQ LED does not blink in the RDY status.
Restarting the SEQUENCE (status: HOLD RUN or RUN RUN)
Functions
! A suspended or running SEQUENCE can be restarted at any
time.
The output is switched to the output on status.
! In this case, all memory locations are executed, one after the
other, from the start address to the stop address, and the
respective values saved to each location (Uset, Iset, tdef/tset
and SSEt) are read out to the power and signal outputs.
Procedure:
With interrupted or running SEQUENCE,
– press the <FUNCTION> key and then browse with the
<> key, the <> or the <FUNCTION> key
until SEq go appears
and execute the command with the <ENTER> key.