User manual

GMC-I Gossen-Metrawatt GmbH 19
5.4 Controlling Output Voltage
Function
Output voltage Uout can be controlled via control inputs Uset+
(non-inverting) and Uset (inverting) with an external control
voltage U
su
.
The following applies during constant voltage operation:
Uout = USET + U
su
k
su
USET: manually selected voltage setpoint value
k
su
: voltage control coefficient = Uout
nom
/ 5 V
Max. setting error: ± 0.05% of U
nom
± 2% of setting value
The voltage control input has been designed as a differential
voltage input:
Uset+: non-inverting input:
U
su
= 0 ... +5 V for Uout = 0 V ... Uout
nom
,
input impedance: 10 kΩ
Uset: inverting input:
U
su
= 0 ... 5 V for Uout = 0 V ... Uout
nom
,
input impedance: 15 kΩ
Notes
The control inputs are not floating inputs, the reference point AGND
is connected to the negative pole of the power output.
Connecting grounded current circuits to the control input may
lead to erroneous settings due to leakage current or earth loops.
If control voltage U
su
is applied to the output’s negative pole with its
reference point at the load side, the inverting input must be
connected to this point (connection b in figure 5.4 a).
Influences caused by voltage drops at the load conductor are
thus avoided.
If control voltage is electrically isolated from the output, connect
Uset to AGND (connection a in figure 5.4 a).
If remote control of output voltage is to be accomplished by means
of a potentiometer, wiring can be implemented in accordance
with figure 5.4 b.
U
su
can be applied as an alternating voltage, e.g. in order to
superimpose the selected direct voltage USET with fault
signals.
The cut-off frequency of the modulated output voltage depends
upon voltage amplitude.
However, the cut-off frequency remains largely independent
of load and the selected current limit thanks to special circuit
technology.
Figure 5.4 a Wiring for control
of output voltage
with an external
voltage
Figure 5.4 b Wiring for control
of output voltage
with an external
potentiometer
5.5 Controlling Output Current
Function
Output current Iout can be controlled with an external control
voltage U
si
via the control input Iset+.
The following applies during constant current operation:
Iout = ISET + U
si
k
si
ISET: manually selected current setpoint value
k
si
: current control coefficient = Iout
nom
/ 5 V
Max. setting error: ±0.1% v. I
nom
± 2% of setting value
Current Control Input
Iset+: non-inverting input:
U
si
= 0 ... +5 V for Iout = 0 A ... Iout
nom
,
Input impedance is equal to 10 kΩ.
Notes
The control input is not a floating input, the reference point AGND is
connected to the negative pole of the power output.
Connecting grounded current circuits to the control input may
lead to erroneous settings due to leakage current or earth loops.
Control voltage U
si
may not be connected to the input’s negative
pole at the load side (see figure 5.5 a).
If remote control of output current is to be accomplished by means
of a potentiometer, wiring can be implemented in accordance
with figure 5.5 b.
U
si
can be applied as an alternating voltage, e.g. in order to
superimpose the selected direct current ISET with fault signals.
The cut-off frequency of the modulated output current depends
upon the load-related voltage amplitude.
CAUTION!
Control inputs Uset +, Uset – and Iset + should only be connected with
shielded cable.
Connect the shield to reference point AGND.
Figure 5.5 a Wiring for control
of output current
with an external
voltage
Figure 5.5 b Wiring for control
of output current
with an external
potentiometer
SLP-KONSTANTER SLP-KONSTANTER
Einstellung
USET = 0
ISET = Isoll
OUTPUT on / off
+SENSE
-OUT
-OUT
-SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN +
TRG IN -
+ 15 V
AGND
Uset -
Uset +
Iset +
U-MON
I-MON
+OUT
+OUT
Einstellung
USET = 0
ISET = Isoll
OUTPUT on / off
+SENSE
-OUT
-OUT
-SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN +
TRG IN -
+ 15 V
AGND
Uset -
Uset +
Iset +
U-MON
I-MON
+OUT
+OUT
Last
Uout
Iout
Uout
Last
a)
I
out
I
su
b)
REF 02
IN
OUT
+5V
2k
Output
Output
U
su
USET+
USET-
AGND
ISET+
AGND
SLP-KONSTANTER SLP-KONSTANTER
Settings
USET = Uset
ISET = 0
OUTPUT ON/OFF
+SENSE
-OUT
-OUT
-SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN +
TRG IN -
+ 15 V
AGND
Uset -
Uset +
Iset +
U-MON
I-MON
+OUT
+OUT
Uout
Load
Settings
USET = Uset
ISET = 0
OUTPUT ON/OFF
Uout
+SENSE
-OUT
-OUT
-SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN +
TRG IN -
+ 15 V
AGND
Uset
Uset +
Iset +
U-MON
I-MON
+OUT
+OUT
I
si
Iout
U
si
REF
02
IN
OUT
+5V
2k
Load
Iout
Output
Output