User Manual
26
Topmost display
Middle display
No. Undermost display
(Selection,
* = default)
Meaning
Hints
Operating mode of both digital outputs
“out.1” and “out.2”
/
Output switched-off Simulation via interface module is still
possible
Energy pulse output The output generates energy pulses
depending on the rate set under .
The meter measurands to output may be
selected under .
*
Alarm output If the alarm limit is exceeded the output
will be active (current flows). If the measur-
and is below limit the output will be
passive. The source of the monitored is
selected under .
(mode)
Alarm supervision source This selection is presented only if operating
mode is set to ALM previously
/
Frequency
Neutral current
Apparent power interval
Reactive power interval
Active power interval
Power factor (cos ϕ)
Apparent power
Reactive power
Active power
Line-neutral voltage
*
Voltage
Average current (bimetal)
Phase current
Line-to-line voltage
Alarm limit for ON-state
The maximum values of the alarm limits
depend on the possible measuring range
(fixed by hardware), converted into possible
primary values given by the selected system
configuration and transformation ratios.
Alarm limit for OFF-state
/
*
*
/
12
11
9
10
8
7
Line Type
'
1L',
'3Lb',
'4Lb'
'4Lu''3Lu'
: 'A.on'= OR-operation of line-measurands
'A.off'= AND-operation of line-measurands
10
9
8
7