User Manual

23
Display and operating
Available measurement data
Example
display
top
Example
display
centre
Example
display
bottom
Units
display
System
display
Phase voltages U1, U2, U3 230 231 229 V
Maximum value U1
max.
, U2
max.
, U3
max.
235 236 231
V
Minimum value U1
min.
, U2
min.
, U3
min.
227 226 225
V
Delta voltages U12, U23, U31 400 402 398 V Δ
Maximum values U12
max.
, U23
max.
, U31
max.
405 406 403
Minimum values U12
min.
, U23
min.
, U31
min.
395 397 396
Phase current I1, I2, I3 2.35 2.37 2.34 A
Maximum values I1
max.
, I2
max.
, I3
max.
2.39 2.40 2.38
A
Average values I1
avg
, I2
avg
, I3
avg
(bimetal -15 min.)
2.04 2.05 2.07
A
Max. average values I1
avgmax.
,
I2
avgmax.
, I3
avgmax.
(slave pointer-15 min.)
2.07 2.05 2.04
A
Neutral current IN
0.45 A
Active powers P1, P2, P3 56.1 56.2 56.5 kW
Maximum values P1
max.
, P2
max.
, P3
max.
60.5 60.4 60.3
kW
Active power system P 125 kW
Maximum value P
max.
239
kW
Reactive power Q1, Q2, Q3 1.24 1.23 1.22 VAr
Maximum values Q1
max.
, Q2
max.
, Q3
max.
1.51 1.52 1.54
VAr
Reactive power system Q 1.54 VAr
Maximum value Q
max.
2.31
VAr
Apparent power S1, S2, S3 2.56 2.58 2.60 VA
Maximum values S1
max.
, S2
max.
, S3
max.
3.43 3.44 3.67
VA
Apparent power system S 5.33 VA
Maximum value S
max.
6.23 VA
Power factor PF1, cos 0.87
Power factor PF2, cos 0.88
Power factor PF3, cos 0.89
Power factor system PF, cos 0.88
Minimum value power factor inductive 0.76
Minimum value power factor capacitive
0.84
Frequency, F 49.99 Hz
Active energy incoming EP high tariff 4589 2356
kWh
Active energy incoming EP low tariff *) 1234 5678
kWh
Active energy outgoing EP high tariff 4589 2356 kWh
Active energy outgoing EP low tariff *) 1234 5678 kWh
Reactive energy inductive EQ high tariff 9876 5432
kVarh
Reactive energy inductive EQ low tariff *) 1234 9876 kVarh
Reactive energy capacitive EQ high tariff 9876 5432
kVarh
Reactive energy capacitive EQ low tariff *) 1234 9876
kVarh
5 active power intervals Pint0, Pint1, …
234 kW
5 reactive power intervals Qint0, Qint1, …
123 VAr
5 apparent power intervals Sint0, Sint1, …
10.1 VA
*) Tariff switching via digital input only (optional extension module required)
Power factor
cos 4 quadrant
operation
P
P
P
P
System
Phase 1
Phase 2
Phase 3
P
Units display
System display
Up key
Down key
Key for
programming
and display
7-segment
display
top
centre
bottom
Display and operating
are identical for the
SINEAX A 210 and
A 220
Determination of measured quantities: The calculation of the measurements is made in accordance with DIN 40 110, with the exception
of the reactive power. This is calculated by the SINEAX A 210/A 220 as a signed value.
Transducers and displays can possibly display different values for the reactive power in the same power system.
The reason is the different calculation methods.