User Manual
21
Energy meter
High tariff
Low tariff
Current
time t
t-0 t-1 t-2 t-3 t-4
Interval 0
Interval 1
Interval 2
Interval 3 Interval 4
Zero value suppression
PF resp. cos : Display ---, if Sx < 0.2% Snenn
Currents: Display 0, if Ix < 0.1% Inenn
Commissioning
The multi-functional power monitor is made operational by swit-
ching on the power supply. The following appears sequentially on
the display:
1. Segment tests: all the segments of the displays and all the LEDs
are lit for 2 s.
2. Version of the software: e.g. A 210 1.04
3. The 3 line voltages at switching on.
Loss of the power supply
All the values configured remain during a loss of the power
supply. On reconnecting the power supply, the last mode selected
is displayed.
Electrical connections
The electrical connections are identical for the SINEAX A 210 and
A 220).
U1
I1
U2
I2
U3
I3
N
Power supply
Pulse /
Limit value output
Measuring input, acc. to measuring mode
Jumper
1 2 +
No. 1
2022 21
12
SO
LOCK
3,7
Camille Bauer AG
Switzerland
14 15
11
N
9
I3
8
U3
7
I3
6
I2
5
U2
4
I2
3
I1
2
U1
1
I1
SINEAX A230
3~500/290V 5A 50/60Hz CAT III
Mat: 123456/1234567/123
Man: 10/02
100-230V AC/DC
50-400Hz 3VA
Connecting modes
L1
N
kl
KL
211 31
Single phase
AC system
L1
N
v
V
u
U
kl
KL
211 31
System/
application
Terminals
L1
L2
L3
5
1
8
2
3
L1
L2
L3
kl
KL
5
1
8
2
3
L1
L2
L3
u
U
v
V
v
V
u
U
k
l
KL
5
1
8
2
3
L1
L2
L3
5
1
8
2
3
7
9
L1
L2
L3
kl
KL
kl
KL
5
1
8
2
3
7
9
L1
L2
L3
u
U
v
V
v
V
u
U
kl
KL
kl
KL
5
1
8
2
3
7
9
L1
L2
L3
kl
KL
kl
KL
xxx
uuu
X
XX
UUU
5
1
8
2
3
7
9
3wire
3 phase
symmetric
load
I: L1
Connect the voltage according to the
following table for current measurement in L2
or L3:
Current Terminals 2 5 8
transf.
L2 1 3 L2 L3 L1
L3 1 3 L3 L1 L2
L1
N
211 31
3 wire
3 phase
asymmetric
load