Datasheet

Camille Bauer Data Sheet A 210/A 220 Le – 06.10 5
SINEAX A 210 / A 220
Multifunctional Power Monitor
Accuracy data
Reference conditions acc. to IEC 688 resp. EN 60 688
Sine 50 - 60 Hz, 15 - 30°C, application group II
Measurement accuracy (related to nominal value)
Current, voltage ± 0.5%
Power ± 1.0%
Power factor ± 1.0%
Energy ± 1.0%
Frequency ± 0.02 Hz (abs.)
Mechanic
Dimensions A 210: 96 x 96 x 46 mm;
Panel cutout
92
+0.8
x 92
+0.8
mm
A 220: 144 x 144 x 46 mm;
Panel cutout
138
+1
x 138
+1
mm
Terminals:
Inputs Screw terminals
Wire gauge single wire:
0.5 - 2.5 mm
2
Wire gauge fi ne wire:
0.5 - 1.5 mm
2
Power supply, outputs Clamps
Wire gauge single and fi ne wire:
0.5 - 1.5 mm
2
Housing material: ABS
flammability class V-0 acc. to
UL 94, self-extinguishing, non-
dripping, free of halogen
Weight: 250 g at A 210 resp.
300 g at A 220
Mounting: For control panel mounting
Environmental conditions
Operating temperature: – 10 to + 55 °C
Storage temperature: – 25 to + 70 °C
Humidity relative: ≤ 75%
Altitude: 2000 m max.
Indoor use statement
Display levels: e.g. 4-wire unbalanced load
P
abcdef
1
U1
U2
U3
U1
max.
U2
max
U3
max
U1
min.
U2
min.
U3
min.
U12
U23
U31
U12
max.
U23
max.
U31
max.
U12
min.
U23
min.
U31
min.
2
I1
I2
I3
I1
max.
I2
max
I3
max
I1
avg
I2
avg
I3
avg
I1
avgmax.
I2
avgmax.
I3
avgmax.
IN IN
max.
3
P1
P2
P3
P1
max
P2
max.
P3
max
PP
max.
4
Q1
Q2
Q3
Q1
max.
Q2
max.
Q3
max
QQ
max.
5
S1
S2
S3
S1
max.
S2
max
S3
max.
SS
max.
6 PF1 PF2 PF3 PF PF
minind
PF
mincap
7F
8
EPinc HT
1
EP inc LT
2
EP out HT
1
EP out LT
2
9
EQ ind HT
1
EQ ind LT
2
EQ cap HT
1
EQ cap LT
2
10
P
Q
PF
P
S
F
11 Pint0 Pint1 Pint2 Pint3 Pint4
12 Qint0 Qint1 Qint2 Qint3 Qint4
13 Sint0 Sint1 Sint2 Sint3 Sint4
1
HT = High tariff
2
LT = Low tariff
Safety
Protection class: II (voltage inputs with protection
impedances)
Measuring category: III
Pollution degree: 2
Measurement voltage: 300 V
Test voltage: Between current inputs, power
supply, digital outputs, terminals of
the plugged-in module: 3700 V /
50 Hz / 1 min.
On voltage inputs:
4.25 kV 1.2/50 μs
Module connections: The pin rail at the back is connected
to the voltage inputs via a protec-
tion impedance. Only the permitted
modules can be plugged-in!
Enclosure protection: Front IP 66, terminals IP 20
Inputs, outputs and power supply are electrically isolated. The
current inputs are electrically isolated from each other.