Datasheet

Camille Bauer Data Sheet A 210/A 220 Le – 06.10 3
SINEAX A 210 / A 220
Multifunctional Power Monitor
Technical data
System/application
Single-phase, 3-wire balanced or unbalanced, 4-wire balanced or
unbalanced, 4-quadrant operation
Measurements available
Measured quantities Measuring path max min
Voltage 1-N, 2-N, 3-N
●●
Voltage 1-2, 2-3, 3-1
●●
Current 1, 2, 3, N
Current I
avg
(bimetal -15 min/
slave pointer)
1, 2, 3
Active power P 1, 2, 3, ∑
Reactive power Q 1, 2, 3, ∑
Apparent power S 1, 2, 3, ∑
cosϕ (4-quadrant display)
1, 2, 3, ∑
cosϕ inductive min.
1, 2, 3
cosϕ capacitive min.
1, 2, 3
Frequency U, I
P-meter incoming/outgoing (HT/
NT)
Q-meter ind./cap. (HT/NT)
5 active power interval value
5 reactive power interval values
5 apparent power interval values
Programmable values (basic unit)
Trip points, pulse rate, transformer ratio, type of system, interval
time for average power values.
Programming can be locked with a jumper at the back of the
instrument.
However, the limit values can still be changed.
All min. and max. values and the counter values can be reset.
The resetting of the counter values can also be blocked with the
above mentioned jumper.
All the measurands, the selected display, the counter values and
the programmed data are kept on a power failure.
Factory default
Brightness: (mid setting)
Limit value / S01: Off
Limit value / S02: Off
Transformer ratio: 1 : 1
Jumper: Not in the LOCK position
Connecting mode: 4-wire asymmetric load
Synchronizing interval: 15 min.
Applicable regulations and standards
IEC 1010 resp. Safety regulations for electrical measuring,
EN 61 010 control and laboratory equipment
EN 60 529 Protection types by case
DIN 43 864 Current interface for the transmission of im-
pulses between impulse encoder counter and
tarif meter (S0 output)
DIN 40 110 AC quantities
IEC/EN 61326-1 Electrical equipment for measurement,
IEC/EN 61326/A1 control and laboratory use, EMC require-
ments
EN 60 688 Electrical measuring transducers for converting
AC electrical variables into analogue and digital
signals
IEC 68-2-1/-2/-3/-6/-27
resp.
EN 60 068-2-1/-2/-3/-6/-27
Ambient tests
-1 Cold, -2 Dry heat,
-3 Damp heat, -6 Vibration,
-27 Shock
Measuring inputs
Nominal frequency: 50, 60 Hz
Nominal input voltage: Phase-phase: 500 V
Phase-N: 290 V
Nominal input current: 5 A or 1 A
Waveform: Sine
Own consumption: Current circuit: ≤ I
2
· 0.01 Ω
Voltage circuit: ≤
U
LN
2
300 kΩ
Continuous overload withstand
10 A at 346 V in single-phase AC system
10 A at 600 V in three-phase system
Short duration overload withstand
Input variable Number of
applications
Duration of
overload
Interval between
two overloads
577 V LN 10 1 s 10 s
100 A 10 1 s 100 s
100 A 5 3 s 5 min.
Measuring range
U, I, S: ≤ 120% of nominal value
P, Q: ≤ ± 120% of nominal value
F: 45 to 65 Hz
cosϕ: ± 1
Overload indicator: oL
The frequency is measured from the current or voltage. The volt-
age has priority.