User Manual
GMC-I Messtechnik GmbH 43
10.6 Executing and Evaluate Test Steps
Manual evaluation of visual inspection
(Prerequisite: sequence parameter „visual inspection“ has been
preset to „on“)
➭ Evaluate the visual inspection.
➭ If you mark even one visual inspection as not passed
with the key shown at the right, the sequence is aborted and
the test is evaluated as not passed.
➭ Resume the test sequence.
Test Steps with Manual Evaluation (e.g. R
PE
)
➭ Observe instructions which appear at the display, e.g.
prompting to contact parts with test probe P1.
If the measured value appears green at the display, it lies within
the limits specified by the standard.
➭ The measured value recording symbol appears in the
softkey bar. The 0 indicates that no measured values
have thus far been saved to buffer memory.
➭ Each time this key is pressed, the measuring or evaluation
procedure is restarted.
➭ Initially, the digit blinks (here a 1 without symbol) until
the measured value settles in. The evaluation cycle is
visualized as follows: the progress bar starts at the left-
hand edge of the display and moves to the right. When
it reaches the rightmost position, evaluation has been
completed and the symbol shown at the right appears
with the current number.
➭ Depending on whether you want to delete the last
value saved to the clipboard or all values, press the
symbol with the wastebasket shown at the right an ap-
propriate number of times.
➭ Proceed to the next measurement by pressing the key
shown at the right.
Note
If the measured value appears red at the display, a
limit value has been violated. If you nevertheless
start the evaluation procedure, an error message
appears. You have the option of repeating the evaluation
procedure.
Note
Regarding the test sequence in switch position A6/A7:
Section 5.2 of DIN EN 90974-4expressly stipulates that
the cables have to be bent and twisted over their entire
length during the measurement, in particular in proximity
to the cable glands, in order to be able to detect any
interruptions of the protective conductor.
Test Steps with Automatic Evaluation (R
INS
, I
PE
)
The measured value is ascertained automatically within a speci-
fied period of time. The evaluation cycle is visualized as follows:
the progress bar starts at the left-hand edge of the display and
moves to the right. When it reaches the rightmost position, evalu-
ation has been completed. The test sequence is then automati-
cally resumed.
Manual Evaluation of the Function Test
(Prerequisite: sequence parameter „function test“ has been preset
to „on“)
➭ Evaluate the function test:
➭ If you mark the function test as not passed with the
softkey shown at the right, the sequence is aborted and the
test is evaluated as not passed.
➭ If you evaluate the function test as passed, you can
simply continue with the test sequence.
In either case you can enter a comment, which can be
subsequently edited as well.
10.7 Ending the Test Sequence
“Sequence finished” appears at the display.
Initial Display (memory screen)
Display of the memory screen depends on the setting in the setup
menu in the SETUP switch position:
Setup 1/3 > Auto. measurements > At end of sequence > Memory
screen.
If set to Results list, the above display is skipped and the results list
shown below is displayed.
You can also access the results list by pressing the key
shown at the right.
0
1
1