Operation Manual
44 GMC-I Messtechnik GmbH
R
PE
PE Resistance
Permanent Connection
Permanently installed DUT
Probe connected to sockets 1 and 2
Permanent Connection and Ground
Probe connected to sockets 1 and 2
Clip-on ammeter connected to sockets 3 and 4
Sequence – Permanently Installed DUT
Ð Select the test: R PE softkey.
Ð Connect the DUT to the mains outlet.
Ð Select measuring range and measurement duration.
Ð Select permanent connection* as the type of connection via
measurement type.
Attention!
!
Deactivate the electrical system which supplies power to
the device under test before connecting the test system (via
the probe)!
Ð Contact one of the conductive parts of the housing which is
connected to the protective conductor with the probe.
Ð Start the test: Press the ONSTART key.
Ð All measured values are displayed.
Ð End the test: Press the ONSTART key.
Ð Read the measured value and compare it with the table of
allowable limit values.
* Special Case ’Permanent Connection and Ground’