Operation Manual
30 GMC-I Messtechnik GmbH
12 Multimeter Functions
12.1 Probe Voltage U
probe
 – Max. 300 V
Voltage is measured between the mains PE terminal at the test instrument 
and the probe. In this case the probe can also be used as a phase finder. 
For IEC 61010: A selection can be made with the up scroll key as to 
whether testing will be conducted under normal conditions, or with 
interrupted protective conductor.
For conducting the measurement the DUT must be put into service via 
key   (14).
Start the U
probe
 measurement.
12.2 Alternating / Direct Voltage U
AC/DC
 – Max. 253 V
Direct, alternating and pulsating volt-
ages of up to 253 V can be measured 
between the 2 and 3 connector jacks. 
Furthermore, it is possible to switch be-
tween minimum, maximum and mo-
mentary measured value via key  . 
This is particularly useful in combination 
with the SECULOAD test adapter for weld-
ing equipment (article number Z745V).
Attention!
!
Two procedures are to be distinguished as from firmware version 7.24:
Procedure 1. DUT not connected to test socket (permanent connection)
õ Select switch position VΩ 
and then measurement U
AC/DC
.
õ Connect the measurement cables to jacks 2 and 3.
õ Scan the measuring point with the test probes.
õ Read the measured values.
õ Remove the test probes from the measuring point and pull off the 
measurement cables from jacks 2 and 3.
õ Return to the Multimeter menu with ENTER.
VΩ