Datasheet
GMC-I Messtechnik GmbH 5
PROFITEST MBASE+, MTECH+, MPRO, MXTRA, SECULIFE IP
DIN VDE 0100/IEC 60364-6 Testers
1)
U > 253 V, with 2 or 3-pole adapter only
2)
1
·
/ 2
·
IΔN > 300 mA and 5
·
IΔN > 500 mA and If > 300 mA only up to U
N
≤ 230 V !
IΔN 5
·
300 mA only with U
N
= 230 V
3)
The transformation ratio selected at the clamp (1 ... 1000 mV/A) must be set in the
“Type” menu with the rotary switch in the “SENSOR” position.
4)
at R
Eselektiv
/R
Egesamt
< 100
Key: D = digits, rdg. = measured value (reading)
R
INS
R
INS
. R
E INS
1 ... 999 kΩ
1.00 ... 9.99 MΩ
10.0 ... 49.9 MΩ
1 kΩ
10 kΩ
100 kΩ
I
K
= 1.5 mA 50 kΩ ... 500 MΩ
U
N
= 50 V
I
N
= 1 mA
kΩ range
±(5% rdg.+10d)
MΩ range
±(5% rdg.+1d)
kΩ range
±(3% rdg.+10d)
MΩ range
±(3% rdg.+1d)
ll
1 ... 999 kΩ
1.00 ... 9.99 MΩ
10.0 ... 99.9 MΩ
1 kΩ
10 kΩ
100 kΩ
U
N
= 100 V
I
N
= 1 mA
1 ... 999 kΩ
1.00 ... 9.99 MΩ
10.0 ... 99.9 MΩ
100 ... 200 MΩ
1 kΩ
10 kΩ
100 kΩ
1 MΩ
U
N
= 250 V
I
N
= 1 mA
1 ... 999 kΩ
1.00 ... 9.99 MΩ
10.0 ... 99.9 MΩ
100 ... 500 MΩ
1 kΩ
10 kΩ
100 kΩ
1 MΩ
U
N
= 500 V/
1000 V
I
N
= 1 mA
U
10 ... 999 V–
1.00 ... 1.19 kV
1 V
10 V
10 ... 1.19 kV ±(3% rdg.+1d)
±
(1.5% rdg.+1d)
R
LO
R
LO
0.01 Ω ... 9.99 Ω
10.0 Ω ... 99.9 Ω
10 mΩ
100 mΩ
I
m
≥ 200 mA
I
m
< 200 mA
0.1 Ω ... 5.99 Ω
6.0 Ω ... 100 Ω
U
0
= 4.5 V ±(4% rdg.+2d) ±(2% rdg.+2d)
l
SEN-
SOR
I
L/Amp
0 ... 99.9 mA 0.1 mA
5 ... 1000 mA
3)
±(10% rdg.+8d) ±(4% rdg.+7d)
l
100 ... 999 mA 1 mA ±(10% rdg.+3d) ±(4% rdg.+2d)
0 ... 99.9 A 0.1 A
5 ... 150 A
3)
±(8% rdg.+2d) ±(3% rdg.+2d)
100 ... 150 A 1 A ±(8% rdg.+1d) ±(3% rdg.+1d)
0 ... 99.9 mA 0.1 mA
5 ... 1000 mA
3)
0.05 ... 10 A
3)
0.5 ... 100 A
3)
5 ... 1000 A
3)
±(7% rdg.+8d) ±(4% rdg.+7d)
l
100 ... 999 mA 1 mA ±(5% rdg.+3d) ±(2% rdg.+2d)
1.0 ... 9.99 A 0.01 A ±(4% rdg.+2d) ±(2% rdg.+2d)
10.0 ... 99.9 A 0.1 A ±(4% rdg.+2d) ±(2% rdg.+2d)
100 ... 999 A 1 A ±(4% rdg.+1d) ±(2% rdg.+1d)
1.00 ... 1.02 kA 0.01 kA ±(4% rdg.+1d) ±(2% rdg.+1d)
0 ... 99.9 mA 0.1 mA
1 V/A 30 ... 1000 mA
3)
U
N
= 120/230/
400 V
f
N
= 50/60 Hz
±
(7%
rdg.
+100d)
±
(4%
rdg.
+100d)
l
100 ... 999 mA 1 mA ±(6% rdg.+12d) ±(3% rdg.+12d)
1.0 ... 9.99 A 0.01 A 100 mV/A 0,3 ... 10 A
3)
±(6% rdg.+12d) ±(3% rdg.+12d)
10.0 ... 99.9 A 0.1 A 10 mV/A 3 ... 100 A
3)
±(5% rdg.+11d) ±(2% rdg.+11d)
Uez
0.0 ... 99.0 mV 0.1 mV
400 kΩ 1000 mV
±(3% v.M.+2D) ±(2% v.M.+2D)
100 ... 999 mV 1 mV ±(3% v.M.+1D) ±(2% v.M.+1D)
Func-
tion
Measured
Quantity
Display Range
Reso-
lution
Input
Impedance/
Tes t Cur rent
Measuring Range Nominal Values
Measuring
Uncertainty
Intrinsic
Uncertainty
Connections
Plug
Insert
1)
2-Pole
Adapter
3-Pole
Adapter
Probe
Clamps
WZ12C Z3512A
MFLEX
P300