14.10.3 Test Sequence PRCD-S (single phase) – 11 Test Steps
Selection Examples
Simulation Interruption (Steps 1 to 6)
Simulation Conductor Exchange (Step 7)
Simulation PE to Phase (Step 8)
Contacting Key ON at PRCD with Probe (Step 10)
Measurement of Protective Conductor Current with a Current
Clamp Transformer (Step 11)
14.10.4 Test Sequence PRCD-S (three-phase) – 18 Test Steps
Selection Examples
Simulation Interruption (Steps 1 to 10)
Simulation Conductor Exchange (Steps 11 to 16)
Simulation PE to Phase (Step 17)
Measurement of Protective Conductor Current with Current Clamp
Transformer (Step 18)
Semi-automatic Change of Fault Simulations (Statuses)
As an alternative to changing
manually between the fault sim-
ulations via the parameter menu
of the respective PRCD selec-
tion PRCD-S 1~, PRCD-K 1~ or
PRCD-S 3~ at the test instru-
ment, it is possible to switch
quickly and conveniently
between the fault simulations.
Select status parameter AUTO
for this purpose. After replying
to and storing each visual
inspection, an automatic
switch-over to the next fault simulation takes place. Individual fault
simulations can be skipped by pressing key I
N
at the test instru-
ment or at the test plug.