Datasheet
GMC-I Messtechnik GmbH 5
PROFITESTINTRO
Tester, IEC 60364-6 / DIN VDE 0100-600
Characteristic Values
1
U > 230 V with KS-PROFITEST INTRO only
2
1
·
/ 2
·
IΔN > 300 mA and 5
·
IΔN > 500 mA and If > 300 mA only up to U
N
230 V!
IΔN 5
·
300 mA where U
N
= 230 V only
Key: d = digits, rdg. = measured value (reading)
Reference Conditions
Line voltage 230 V 0.1%
Line frequency 50 Hz 0.1%
Meas. quantity frequency
45 Hz 65 Hz
Measured qty. waveform
Sine (deviation between effective and
rectified value 0.1%)
Line impedance angle cos =1
Supply voltage 12 V 0.5 V
Ambient temperature +22 C 3 K
Relative humidity 45% 10%
Nominal Ranges of Use
Voltage U
N
120 V (108 ... 132 V)
230 V (196 ... 253 V)
400 V (340 ... 440 V)
Frequency f
N
16⅔ Hz (15.4 ... 18 Hz)
50 Hz (49.5 ... 50.5 Hz)
60 Hz (59.4 ... 60.6 Hz)
200 Hz (190 ... 210 Hz)
400 Hz (380 ... 420 Hz)
Overall voltage range U
Y
65 ... 550 V
Overall frequency range 15.4 ... 420 Hz
Waveform Sinusoidal
Temperature range 0 C ... + 40 C
Supply voltage 8 ... 12 V
Line impedance angle Corresponds to cos = 1 ... 0.95
Power Supply
Batteries, rechargeable
NiMH batteries 8 each AA 1.5 V
We recommend using the battery pack
(article number: Z502H).
Number of measurements (standard setup with illumination)
– For RINS 1 measurement – 25 s pause:
Approx. 600 measurements
– For R
LO
Auto polarity reversal / 1
(1 measuring cycle) – 25 s pause:
approx. 800 measurements
Battery test Symbolic display of battery voltage
Power management
Display illumination can be switched off.
The test instrument is switched off
automatically after the last key opera-
tion. The user can select the desired
on-time.
Safety shutdown If supply voltage is too low (U < 8.0 V),
the instrument is switched off, or can-
not be switched on.
Recharging socket Installed, optional rechargeable batter-
ies can be recharged directly by con-
necting a charger to the recharging
socket:
Z502R charger
Charging time Z502R charger:
approx. 2 hours *
* Maximum charging time with fully depleted rechargeable batteries.
A timer in the charger limits charging time to no more than 4 hours.
Func-
tion
Measured
quantity
Display Range
Reso-
lution
Input
Impedance /
Test c urre nt
Measuring
Range
Nominal
Values
Measuring
Uncertainty
Intrinsic
Uncertainty
Connections
PRO-
Schuko
adapter
1
KS-
PROFiTEST
INTRO
2-pin 3-pin
RINS
RINS, R
E ISO
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 49.9 M
1 k
10 k
100 k
I
K
= 1.5 mA 50 k... 300 M
U
N
= 50 V
I
N
= 1 mA
k
range
(6% rdg.+10d)
M
range
(6% rdg.+1d)
k range
(3% rdg.+10d)
M
range
(3% rdg.+1d)
ll
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 99.9 M
1 k
10 k
100 k
U
N
= 100 V
I
N
= 1 mA
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 99.9 M
100 ... 200 M
1 k
10 k
100 k
1 M
U
N
= 250 V
I
N
= 1 mA
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 99.9 M
100 ... 500 M
1 k
10 k
100 k
1 M
U
N
= 500 V
U
N
= 1000 V
I
N
= 1 mA
U
10 ... 999 V–
1.00 ... 1.19 kV
1 V
10 V
10 ... 1.19 kV (3% rdg.+1d)
±(1.5% rdg. + 1
d)
R
LO
R
LO
0.01 ... 9.99
10.0 ... 99.9
100 ... 199
10 m
100 m
1
I
m
200 mA
I
m
200 mA
0.20 ... 6.00
6.01 ... 99.9
U
0
= 4.5 V (5% rdg.+2d) (2% rdg.+2d)
l
BAT