Tester, IEC 60364-6 / DIN VDE 0100-600
Sample Displays
Softkeys allow for convenient selection of sub-functions and
parameter settings. Unavailable sub-functions and parameters
are automatically prevented from appearing at the display.
Applicable Regulations and Standards
Characteristic Values
Nominal Ranges of Use
Voltage U
N
120 V (108 132 V)
230 V (196 253 V)
400 V (340 440 V)
Frequency f
N
16⅔ Hz
(15.4 18 Hz)
50 Hz (49.5 50.5 Hz)
60 Hz (59.4 60.6 Hz)
200 Hz (190 210 Hz)
400 Hz (380 420 Hz)
Overall voltage range
65 550 V
Overall frequency range 15.4 420 Hz
Waveform Sinusoidal
Temperature range 0 C +40C
Battery voltage 8 12 V
Line impedance angle Corresponds to cos =1 0.95
RCD Measurement Display Loop Resistance
Measurement Display
Earthing Resistance Low-Resistance
Measurement Display Measurement Display
Insulation Measurement Display Voltage Measurement Display
IEC 61010-1/EN 61010-1/
VDE 0411-1
Safety requirements for electrical equipment for mea-
surement, control and laboratory use
Part 1: General requirements
(IEC 61010-1:2010 + Cor. :2011)
Part 31: Safety requirements for hand-held probe as-
semblies for electrical measurement and test
(IEC 61010-031:2002 + A1:2008)
IEC 61557/ EN 61557/
VDE 0413
Part1: General requirements (IEC 61557-1:2007)
Part 2: Insulation resistance (IEC 61557-2:2007)
Part 3: Loop impedance (IEC 61557-3:2007)
Part 4: Resistance of earth connection and equipotential
bonding
(IEC 61557-4:2007)
Part 5: Resistance to earth (IEC 61557-5:2007)
Part 6: Effectiveness of residual current devices (RCD) in
TT, TN and IT systems
(IEC 61557-6:2007)
Part 7: Phase sequence (IEC 61557-7:2007)
Part 10:Electrical safety in low voltage distribution sys-
tems up to 1000 V AC and 1500 V DC – Equip-
ment for testing, measuring or monitoring of pro-
tective measures (IEC 61557-10:2000)
EN 60529
VDE 0470-1
Test instruments and test procedures
Degrees of protection provided by enclosures (IP code)
DIN EN 61326-1
VDE 0843-20-1
Electrical equipment for measurement, control and labo-
ratory use –EMC requirements – Part 1: General require-
ments
per IEC 60364-6
VDE 0100-600
Low-voltage electrical installations
– Part 6: Tests
EN 50110-1
VDE 0105-1
Operation of electrical installations
– Part 1: General requirements
IEC 60364-7-710
VDE 0100-710
Low-voltage electrical installations
– Requirements for special installations or locations –
Part 710: Medical locations