4.3.1 Setting Test Parameters
MENU
Select Parameter
Set Value
Significance of Parameters
U
ins[nom]
Nominal insulation voltage
100/250/500 V, 1.00/1.50/2.00/2.50/5.00 kV
PI(t2/t1) Polarization index PI is the relationship between insula-
tion resistance values measured after 1 minute PI(t1),
and after 10 minutes PI(t2). Other durations can be
selected if required.
PI (limit) Selected polarization index limit value: appears in the
footer in the measuring menu
DAR(t2/t1) Absorption ratio DAR is the relationship between insu-
lation resistance values measured after 30 seconds
DAR(t1), and after 60 seconds DAR(t2). Other dura-
tions can be selected if required.
DAR (limit) Selected absorption ratio limit value: appears in the
footer in the measuring menu
For resetting parameter values to default setting, see page 22.
4.3.2 Starting the Test
START
The two countdown timers (10:00 and 02:00) display remaining
test time for each respective function.
STORE
Press briefly: Save results
Press & hold: Save results and activate the entry field:
A description of the measurement with up to 15
characters can be entered to the information field
at the bottom. See chapter 5.1.1 regarding entry.