Operation Manual
30 GMC-I Messtechnik GmbH
Attention!
!
Do not touch the test probes during measurement!
A direct voltage of up to 5000 V is present between the
test probes.
Note
Testing the Measurement Cables:
Initial testing should be performed after short-circuiting
the measurement cables with their test probes. The
instrument should display nearly zero MΩ. A broken mea-
surement cable can be detected in this way.
TEST
Select the Test
MENU
Open the Submenu
4.1.1 Setting Test Parameters
The type of utilized test voltage can be selected here:
• Fixed test voltage
• Variable test voltage
(e.g. lower test voltage for voltage-sensitive components)
• Test voltage in a sequence of steps (U
STEP
= step voltage), e.g. in
order to allow for better evaluation of insulation quality with re-
gard to dielectric strength
Additional parameters must be set as well depending upon the
selected type of test voltage.
MENU
Select Parameter
Set Value