Brochure
Overview of the Most Important Functions
Type Measuring
Voltage
Measuring Range
CAT Low-
Resistance
Measurement
Polarization
Index PI
Absorption
Ratio DAR
Voltage
Measurement
USP´s
Backlit
Display
Offset
Test Resistor VDE0105
Intelligent Filter
Electronic Fuse
250, 500, 1000 V
10 k
Ω ... 10 GΩ
CAT IV 300 V /
CAT III 600 V
0.17 Ω … 10 Ω 10 V … 500 V
n n
– –
n
50 to 500 V (BASE)
50 to 1000 V (TECH)
10 kΩ ... 100 GΩ (BASE)
10 k
Ω ... 200 GΩ (TECH)
CAT IV 300 V /
CAT III 600 V /
0.17 Ω … 10 Ω
10 V … 500 V /
10 V … 1000 V
n n n n n
with Memory
50 to 1000 V
(50, 100, 250, 500,
1000)
Uvar, Uramp
10 kΩ ... 1TΩ
CAT IV 300 V /
CAT III 600 V /
0.17 Ω … 10 Ω
PI, DAR
10 V … 1000 V
n n n n n
50 to 1000 V
(50, 100, 250, 500,
1000)
10 k
Ω ... 1TΩ
CAT IV 300 V /
CAT III 600 V /
0.17 Ω … 4 Ω 10 V … 1000 V
n n n n n
50 to 1000 V
(50, 100, 250, 500,
1000)
10 k
Ω ... 1TΩ
—
0.17 Ω … 10 Ω
PI, DAR
10 V … 1000 V –
n
–
n n
100 to 5000 V
(100, 250, 500, 1000
1500, 2500, 5000)
10 k
Ω ... 1TΩ
CAT IV 300 V /
CAT III 600 V
—
0 … 2000 V
AC / DC
15 ... 500 Hz
– – – – –
100 V ... 5000 V
(100, 250, 500, 1000
1500, 2500, 5000)
0.4 M
Ω ... 1TΩ
Uvar
CAT IV 300 V /
CAT III 600 V
PI, DAR
Capacitance
Measurement
50 V … 5 kV DC
50 V ... 1 kV
AC / DC
15 ... 500 Hz
n
– – – –
Measurements which are more and more in demand:
The polarization index (PI) is a long-term insulation measurement, during which measured values obtained after one minute and after ten
minutes are compared with each other.
Insulation resistance values acquired over a period of ten minutes may provide information regarding defects, as well as penetration by
contamination or moisture. If the insulation is intact, insulation resistance is initially low, and then increases. The curve usually flattens
out in the case of contamination or moisture. IEEE standard 43-2000 specifies reference values for measurements at motors and
generators.
These measurements can be performed with the METRISO XTRA and Metriso PRIME+ with any measurement voltage. Whereas the
polarization index (PI) is used with preference for large objects, the dielectric absorption ratio (DAR) serves as a subset of the polarization
index for smaller machines. In this case, insulation resistance measurements after 30 and 60 seconds are compared with each other.