Operation Manual
24 GMC-I Messtechnik GmbH
10 Characteristic Values
1)
Display range up to 600 V
2)
Display range up to 1.2 kV
3)
the indicated accuracy is only achieved with the shielded high-resistance measur-
ing cable KS-C (article no. Z541F)“
4)
does not conform to DIN EN 61557-2
5)
up to 5 Ω
Meas.
Qty.
UiSO Range Measuring Range
Reso-
lution
Open-Circuit
Voltage U
0max
Test
Current
Intrinsic Uncertainty
Measuring
Uncertainty
Overload
Capacity
RINS
BASE/TECH: 50 V
BASE/TECH: 100 V
INTRO: 250 V ... 1000 V
BASE: 250 V / 500 V
TECH: 250 V / 500 V / 1000 V
100 k 10.0 kΩ ... 99.9 kΩ 0.1 k
50 V /100 V:
1.25 U
ISO
250 V /
500 V /
1000 V:
1.1 U
ISO
I
N
= 1 mA
I
K
≤ 5 mA
±(5% rdg. + 3 d) ±(7% rdg. + 3 d)
METRISO BASE:
600 V AC/DC
TRMS
METRISO INTRO
METRISO TECH:
TRMS
1 M 100 kΩ ... 999 kΩ 1 k
10 M 1.00 MΩ ... 9.99 MΩ 10 k
100 M 10.0 MΩ ... 99.9 MΩ 100 k
1 G 100 MΩ ... 999 MΩ 1 M
10 G 1.00 GΩ ... 9.99 GΩ 10 M
100 G 10.0 GΩ ... 99.9 GΩ 100 M ±(8% rdg. + 3 d)
3)
±(10% rdg. + 3 d)
3)
200 G 100 GΩ ... 199 GΩ 1 G ±(25% rdg. + 5 d)
3)
±
(50% rdg. + 20 d)
3) 4)
U
AC/
DC
METRISO BASE
100 V 10.0 V ... 99.9 V 0.1 V
— ±(2.5% rdg. + 3 d) ±(5% rdg. + 3 d)
600 V AC/DC
TRMS
500 V 100 V ... 510 V
1)
1 V
METRISO INTRO
METRISO TECH
100 V 10.0 V ... 99.9 V 0.1 V
— ±(2.5% rdg. + 3 d) ±(5% rdg. + 3 d)
1000 V AC/DC
TRMS
1000 V 100 V ... 999 V
2)
1 V
RLO 10 Ω 0.17 ... 9.99 Ω
0.01
Ω
4 V < U0
< 6 V
200 mA ≤ I
I
≤
260 mA
±(2.5% rdg. + 3 d) ±(5% rdg. + 3 d)
METRISO BASE:
600 V AC/DC
TRMS
METRISO INTRO
METRISO TECH:
1000 V AC/DC TRMS
R
METRISO BASE
METRISO TECH
Display range as of 01.0
Ω
100 Ω 10.0 ... 99.9 Ω 0.1 Ω
U
0
max. 15 V
1 mA ≤ I
I ≤ 1,3 mA
±(2.5% rdg. + 3 d) ±(5% rdg. + 3 d)
METRISO BASE:
600 V AC/DC
TRMS
METRISO TECH
1000 V AC/DC TRMS
1 kΩ 100 ... 999 Ω 1 Ω
10 kΩ 1.00 ... 9.99 kΩ 10 Ω