Datasheet
METRAPHASE 1
Phase Sequence Indicator
3-348-992-03
2/8.99
GOSSEN-METRAWATT GMBH
Applications
Phase sequence, line frequency and phase voltage are tested
and displayed simultaneously after the METRAPHASE 1 test
instrument has been connected to the system under test at all
phases with the included, contact-protected connector cables.
The instrument is suited for initial testing, as well as for testing
after repairs and modifications.
Features
Convenient Testing with Only 2 Cables (2-pole measurement)
In addition to normal testing with 3 measurement cables, phase
sequence can also be tested with only 2 cables. After connection
to L1 has been established, phases L2 and L3 are scanned
separately, one after the other.
This operating mode is indicated by means of intelligent software
which rules out the possibility of erroneous measurements.
Automatic Activation
The instrument is activated automatically as soon as a voltage of
at least 100 V is applied to any 2 measurement sockets.
Battery Saving Circuit
The instrument is shut down automatically when zero voltage is
applied in order to extend battery service life.
Applicable Regulations and Standards
Characteristic Values
IEC 61010-1/EN 61010-1/
VDE 0411-1
Safety requirements for electrical equipment
for measurement, control and laboratory use
IEC 61557 Part 7/
EN 61557-7/
VDE 0413 Part 7
Phase sequence indicators
EN 60529
VDE 0470 Part 1
Test instruments and test procedures
– Protection provided by enclosures (IP code)
EN 50081-1
Electromagnetic compatibility (EMC)
Generic standard for interference emission
EN 50082-1
Electromagnetic compatibility (EMC)
Generic standard for interference immunity
Phase
Direction
Phase
Sequence
Phase Sequence
LED Display
Phase Direction LED Display
Clockwise L1 – L2 – L3 L1 L2 L3 light up
green LED rotates
in clockwise direction
Counterclock-
wise
L3 – L2 – L1 L1 L2 L3 light up
red LED rotates
in counterclockwise direction
Asymmetrical Lx – N/PE – Lx
connection with
N/PE not indicated
green or red LED rotates
clockwise or counterclockwise
depending upon connection
Phase Missing Lx – X – Lx
missing phase
does not light up,
the other 2 do
light up
—
• Displays phase sequence
by means of 6 optically rotating LEDs with different colors
(clockwise: green, counterclockwise: red)
• Displays nominal line voltage
with 3 LEDs
• Displays nominal line frequency
with 6 LEDs
• Phase search
with 3 LEDs for L1, L2 and L3
• Indication of errors for:
– Asymmetries
– Missing phases
Useful accessories
• Tester for meter start-up testing
• Mains power pack for continuous operation