4 Technical Data
4.1 Measuring Functions
Residual Current Devices (RCD) – General Specifications
Nom. residual current 10, 30, 100, 300, 500 mA
Deviation from nominal
residual current (–0/+0.1)I; I= I
N
, 2x I
N
, 5x I
N
Waveform of the nom.
residual current Sinusoidal (AC), pulsating DC (A)
RCD type Standard and selective S
Initial polarity of
the residual current 0° or 180°
Voltage range 190 V to 255 V / 45 to 65 Hz
Residual Current Generated by the Tester (TRMS value at 20 ms):
Touch Voltage Uc and Uci
Nominal range per EN 61557-6 – 3.0 to 49.0 V for a touch volt-
age limit value of 25 V
Nominal range per EN 61557-6 – 3.0 to 99.0 V for a touch volt-
age limit value of 50 V
Impedance of the Fault Loop RL
Nominal range per EN 61557-3 – 27 to 2000
Measuring current: ½ I
N
The results of the fault loop impedance measurement appear at
the display if nominal residual current is set to I
N 30 mA.
Time to Trip – TIME
Standard Residual Current Circuit Breaker (range per EN 61557-6):
Selective Residual Current Circuit Breaker (range per EN 61557-6):
Tripping Current I
Range per EN 61557-6
Alternating Voltage (frequency range: 45 to 65 Hz)
Key
a) In the case of alternating quantities, the TRMS voltage value is
measured.
b) The measuring uncertainties specified here are only valid if line
voltage is stable during measurement, the earthing system is
free of interference voltage, there are no influences caused by
potential from neighboring systems and no leakage current
flows through the measured electrical circuit.
c) rdg. means reading, i.e. measured value, D = digits (i.e. num-
ber of the decimal place with the least significance)
4.2 General Data
Reference Conditions
Temperature 23 ± 2° C
Relative humidity 40 to 60%
Device position any
Ambient Conditions
Operating Conditions
Operating temperature
0 to 40° C
Relative Humidity max. 85%, no condensation allowed
Device position any
Storage Conditions
Temperature -10 to 70° C
Relative Humidity max. 90% at -10 to +40° C
max. 80% at +40 to +70° C
Device position any
Power Supply
Batteries 4 ea. AAA (LR03), 1.5 V alkaline or
1.2 V NIMH (with at least 750 mAh)
Number of
measurements with batteries at 800 mAh:
approx. 3,000 measurements
Electrical Safety
Measuring category CAT III / 300 V
Pollution degree 2
Protection class II
Fuse SIBA ceramic fuse
6.3 mm x 32 mm, F1 A/600 V
switching capacity 50 kA at 600 V
Mechanical Design
Display OLED, multicolored, graphic
Protection IP 43
Dimensions approx. 260 x 70 x 40 mm
Weight approx. 0.36 kg with batteries
½ I
N
I
N
2 x I
N
5 x I
N
I
IN
(mA)
AC A AC A AC A AC A AC A
10 5 3.5 10 20 20 40 50 100
✓✓
30 15 10.5 30 42 60 84 150 212
✓✓
100 50 35 100 141 200 282 500 —
✓✓
300 150 105 300 424 — — — —
✓✓
500250175500—————
✓
—
Measuring
Range
Resolution Intrinsic Uncertainty Measuring
Uncertainty
0.0 to 9.9 V
0.1 V
-0/+10% rdg. + 2 D -0/+10% rdg. + 3 D
10.0 to 99.9 V -0/+10% rdg. -0/+10%) rdg. + 1 D
Measuring
Range
Resolution Intrinsic Uncertainty Measuring Uncertainty
0 to 2000 1 (5%rdg.+3D+0.05V/
IN) (5%rdg.+5D+0.05V/IN)
Measuring Range Resolution Intrinsic Uncertainty Measuring
Uncertainty
0 to 300 ms
(½I
N, IN)
1 ms 3 ms 4 ms
0 to 150 ms
(2x I
N)
0 to 40 ms
(5x I
N)
Measuring Range Resolution Intrinsic Uncertainty Measuring
Uncertainty
0 ... 500 ms
(½I
N, IN)
1 ms 3 ms 4 ms
0 ... 200 ms
(2x I
N)
0 ... 150 ms
(5x I
N)
Measuring Range
for I
Resolution Intrinsic Uncertainty Measuring
Uncertainty
0.4 to 1.1 I
N
(type: AC)
0.1 mA 0.08 IN 0.1 IN
0.4 to 1.5 I
N
(type: A)
Measuring Range Resolution Intrinsic Uncertainty Measuring
Uncertainty
190 to 255 V 0.1 V 0.08 IN 0.1 IN