User Manual

GMC-I Messtechnik GmbH 3
Use original accessories only.
Maximum permissible voltage between test probe and ground
is 300 V!
Maximum permissible (externally applied) voltage between the
test probes is 600 V!
1.4 Applications
The test instrument is enclosed in a compact housing with a pat-
ented means of retaining the test probes.
The high-contrast, four-color OLED display assures excellent legi-
bility. When performing measurements under unfavorable light
conditions, measuring point illumination can be switched on –
white LED at the front.
The RCD test instrument is capable of the following measure-
ments:
RCD disconnection time
RCD breaking current
Touch voltage
Loop impedance without tripping the RCD
–Phase detection
1.5 Applicable Standards
Measurement EMC Safety
EN 61557-1 EN 55022 class B EN 61010-1
EN 61557-6 EN 61326-1 EN61010-031
1.6 Environment
The shipping package is made of recyclable cardboard. Batteries
must be disposed of in accordance with applicable regulations.
This device may not be disposed of with the trash. Further
information regarding the WEEE mark can be accessed
on the Internet at www.gossenmetrawatt.com by entering
the search term “WEEE”.
2 Device Description
2.1 Housing
Figure 2.1: Top View
For transport purposes, the movable test probe can be attached
to the housing and retained by a magnet such that both metal tips
are simultaneously recessed and protected.
In order to charge batteries which have been inserted into the
instrument, the flexible test probe’s connector plug must be
removed and the slide must be pushed to the left, so that the
socket at the right is made accessible and the charger can be
plugged into it.
Figure 2.2: Detail View of the Back Panel with Battery Compart-
ment Lid
2.2 Operation and OLED Display
1 Graphic OLED display
2 START key:
Switch on:
Press and hold until the display
lights up.
Start measurement:
Press and hold until measurement
starts. Briefly pressing starts mea-
surement if voltage is applied to the
test probes (exception for Uc: is dis-
played immediately after voltage is
applied).
Measurement point illumina-
tion:
Press briefly to switch illumination
on and off.
Switch off:
Press twice briefly to switch the
instrument off.
3 FUNC key for selecting the following
measuring functions: Uc, TIME,
I
4 IN key for selecting nominal
residual current
5 TYPE key:
Uc function:
RCD Type Selection
– TIME function:
Selection of waveform and initial polarity of the residual current, as well as
RCD type
– I function :
Selection of waveform and initial polarity of the residual current
6 xIN key
– Uc function:
Selection of the touch voltage limit value
– TIME function: selection of a multiplier for nom. residual current
Figure 2.3: Control Panel and OLED Display
Figure 2.4: Example of Displayed Information
The information which appears at the display varies depending on
the selected function.
!
Fixed Test Probe Attached to the Device
LED
OLED Display
Socket for Flexible Test Probe
Socket for Charger
P
l
u
g
-
I
n
M
o
b
i
l
e
T
e
s
t
P
r
o
b
e
Plastic
Control Panel
Housing
Screws for Battery Compartment Lid
Battery Compartment Lid
Serial Plate
3
1
2
4
5
6
Battery Display
Measuring
IN and
Temperature Display
RCD Type
Ancillary
Main
Reading
Function
IN
Value
Multi-
pliers
Waveform