Datasheet

Edited in Germany • Subject to change without notice • PDF version available on the Internet
METRALINE RCD
CHECK
RCD Test Instrument
GMC-I Messtechnik GmbH
Südwestpark 15
90449 Nürnberg,
Germany
Phone: +49 911 8602-111
Fax: +49 911 8602-777
e-mail info@gossenmetrawatt.com
www.gossenmetrawatt.com
Impedance of Fault Loop RL
Nominal Range per EN 61557-3 – 27 to 2000
Measuring current: ½ I
N
The results of the fault loop impedance measurement appear at
the display, if nominal residual is set to I
N 30 mA.
Time to Trip – TIME
Standard Residual Current Circuit Breaker
(range per EN 61557-6):
Selective Residual Current Circuit Breaker (range per EN 61557-6):
Tripping Current I (range per EN 61557-6):
Alternating Voltage (frequency range: 45 to 65 Hz)
Key
a) In the case of alternating quantities, the TRMS voltage value is
measured.
b) The measuring uncertainties specified here are only valid if line
voltage is stable during measurement, the earthing system is
free of interference voltage, there are no influences caused by
potential from neighboring systems and no leakage current
flows through the measured electrical circuit.
c) rdg. means reading, i.e. measured value, D = digits (i.e. num-
ber of the decimal place with the least significance)
Reference Conditions
Temperature 23 C
Relative humidity 40 to 60%
Device position any
Electromagnetic Compatibility (EMC)
Interference emission EN 61326-1:2006 class B
Interference immunity
EN 61326-1:
2006
Operating Conditions
Operating temperature
0 to 40 °C
Relative humidity max. 85%, no condensation allowed
Device position any
Storage Conditions
Temperature –10 to +70 °C
Relative humidity max. 90% at -10 to +40 °C
max. 80% at +40 to +70 °C
Device position any
Power Supply
Batteries 4 ea. AAA (LR03), 1.5 V alkaline or
1.2V NIMH (with at least 750 mAh)
Number of
measurements with batteries at 800 mAh:
approx. 3,000 measurements
Electrical Safety
Measuring category CAT III / 300 V
Pollution degree 2
Protection class II
Fuse SIBA ceramic fuse
6.3 mm x 32 mm, F1 A/600 V
switching capacity 50 kA at 600 V
Mechanical Design
Display OLED, multicolored, graphic
Protection Housing: IP 43
Dimensions approx. 260 x 70 x 40 mm
Weight approx. 0.36 kg with batteries
Scope of Delivery
1 Test instrument with mobile test probe incl. 4 batteries (AAA)
1Pouch
1 Condensed operating instructions
1 CD ROM with operating instructions in available languages
1 Factory calibration certificate
Order Information
* with plug adapter for the following countries: EU, UK, US, AU
Meas. Range Resolution Intrinsic Uncertainty Measuring Uncertainty
0 to 2000 1 (5%rdg.+3D+0.05V/
IN) (5%rdg.+5D+0.05V/IN)
Measuring Range Resolution Intrinsic Uncertainty Meas. Uncertainty
0 to 300 ms (½I
N, I
N)
1 ms 3 ms 4 ms
0 to 150 ms (2x IN)
0 to 40 ms (5x I
N)
Measuring Range Resolution Intrinsic Uncertainty Meas. Uncertainty
0 to 500 ms (½I
N, I
N)
1 ms 3 ms 4 ms
0 to 200 ms (2x IN)
0 to 150 ms (5x I
N)
Measuring Range for I
Resolution Intrinsic Uncertainty Meas. Uncertainty
0.4 to 1.1 I
N (type AC)
0.1 mA 0.08 IN 0.1 IN
0.4 to 1.5 IN (type A)
Measuring Range Resolution Intrinsic Uncertainty Meas. Uncertainty
190 to 255 V
0.1 V 0.08 IN 0.1 IN
Description Type Article number
RCD Test Instrument
METRALINE RCD-CHECK
M507B
Broad-range charger for charging
batteries included in the
METRALINE ISO-RCD-Z/CHECK
Input*: 100 to 240 V AC 10%;
Output: 9 V DC, 180 mA Z507A Z507A
4 rechargeable batteries (AAA) for
METRALINE ISO-RCD-Z/CHECK Z507B Z507B