Datasheet
Edited in Germany • Subject to change without notice • PDF version available on the Internet
METRALINE ISO
CHECK
Insulation Measuring Instrument
GMC-I Messtechnik GmbH
Südwestpark 15
90449 Nürnberg,
Germany
Phone: +49 911 8602-111
Fax: +49 911 8602-777
E-mail: info@gossenmetrawatt.com
www.gossenmetrawatt.com
Measurement of Surge Protection Devices
Measuring Method Rising DC voltage when measuring the so-
called milliampere point
Measurement of Direct and Alternating Voltage
(Frequency Range: 45 to 60 Hz)
Key
a) The TRMS value for alternating voltage is measured.
b) rdg. means reading, i.e. measured value.
d = digits (i.e. number of the decimal place with the least significance)
Reference Conditions
Temperature 23 2°C
Relative humidity 40 to 60%
Device position any
Ambient Conditions
Operating Conditions
Operating
temperature 0 to 40 °C
Relative humidity max. 85 %, no condensation allowed
Device position any
Storage Conditions
Temperature –10 to 70 °C
Relative humidity max. 90% at –10 to +40 °C
max. 80% at +40 to +70 °C
Device position any
Power Supply
Batteries 4 ea. AAA (LR03), 1.5 V alkaline or
1.2 V NIMH (with at least 750 mAh)
Number of
measurements with batteries at 800 mAh:
approx. 1,000 measurements
(with 500 V test voltage on 500 k
Electrical Safety
Measuring category CAT III / 300 V or CAT II / 600 V
Pollution degree 2
Protection class II
Protection IP 43
Electromagnetic Compatibility (EMC)
Interference emission EN 61326-1:2006 class B
Interference immunity EN 61326-1:2006
Mechanical Design
Display OLED, multicolored, graphic
Protection Housing: IP 40
per DIN VDE 0470 part 1/EN 60529
Dimensions approx. 260 x 70 x 40 mm
Weight approx. 0.36 kg with batteries
Scope of Delivery
1 Test instrument with mobile test probe
1Pouch
1 CD ROM with operating instructions
in available languages
1 Condensed operating instructions
Order Information
* with plug adapter for the following countries: EU, UK, US, AU
Range Resolution Intrinsic Uncertainty Measuring
Uncertainty
40 to 1050 V 1 V (2% rdg. + 2 d) (3 % rdg. + 3 d)
Range Resolution Intrinsic Uncertainty Measuring
Uncertainty
0 to 600 V 1 V (2% rdg. + 2 d) (3 % rdg. + 3 d)
Description Type Article number
Insulation measuring instrument METRALINE
ISOCHECK M507C
Broad-range charger for charging batteries in-
cluded in the METRALINE ISO-RCD-Z/CHECK
Input*: 100 to 240 V AC 10%;
Output: 9 V DC, 180 mA Z507A Z507A
4 rechargeable batteries (AAA) for