User Manual

24 GMC-I Messtechnik GmbH
Control Functions
4.5.1 Rapid Momentary Value Acquisition for U DC and I DC
Rapid momentary value acquisition is only activated during
memory mode operation in the U DC and I DC functions, and only
after selecting a sampling period of 0.5, 1, 2, 5, 10, 20 or 50 ms:
All trigger and hysteresis functions are available, although the
momentary value is acquired with a separate measuring circuit.
This allows for the recording of the waveshapes of low-frequency
signals with reduced resolution and accuracy (typically < 1% of the
measuring range under reference conditions, not specified).
Roughly 300,000 measured values can be saved in this mode.
Values of up to about 1.9 x Umax or Imax are recorded (with fixed
range, range-dependent fluctuations), and thus the range limit
can be exceeded by approximately 90%.
Note
The ZERO/ΔREL function is not taken into consideration for
rapid momentary value acquisition!
4.5.2 Power and Energy Measurement in the Memory Mode
The value selected for the SEt > EnErGY > StorE menu parameter
specifies which values from power and energy measurements will
be saved during memory mode operation:
SEt > EnErGY > StorE = normal (default setting):
Momentary values for current, voltage, active, reactive and
apparent power, as well as power factor, are acquired and
saved to memory at the selected sampling rate (at least 0.5 s).
SEt > EnErGY > StorE = demand:
The instrument only saves mean power values at the end of the
dEMAnd tiME observation period
(see section 6.4.4, “dEMAnd tiMEparameter).
SEt > EnErGY > StorE = all:
Momentary values are saved at the selected sampling rate and
mean power values are saved at the end of each dEMAnd
tiME observation period
(see section 6.4.4, “dEMAnd tiMEparameter).
Ð Set the dEMAnd tiME interval for memory mode operation
before you start recording.