Datasheet
METRAHITENERGY
TRMS SYSTEM Multimeter
8
GMC-I Messtechnik GmbH
Accessories
NA X-TRA Power Pack (90 ... 250 V AC / 5 V DC)
Power pack for battery-saving
mains operation, for continuous
measurement using multimeters
with internal memory
• Broad range input, 50/60 Hz
• Measuring category: CAT IV at
600 V
PMA16 Power Measuring Adapter
The adapter is used for safe, trouble-free
measurement of current consumption
(up to 16 A) at earthing contact plugs, as
well as for connecting the voltage path
to the METRAHIT ENERGY for power mea-
surement.
Accessories for Operation at a PC
Interface Adapter for USB Connection
The following functions can be executed with the USB X-TRA
bidirectional interface adapter:
• Configure the METRAHIT multimeter from a PC.
• Transmit live measurement data to the PC.
• Read data out of memory from the METRAHIT ENERGY.
The adapter does not require a separate power supply.
Its baud rate is 38,400 baud.
A CD ROM is included which contains current drivers for
Windows operating systems.
METRAwin
10/METRAHit
Software
METRAwin
10/METRAHit
PC software is a multilingual,
measurement data logging program for recording, visualizing,
evaluating and documenting measured values with reference to
time from METRAHIT E series multimeters.
Communication between the PC and the measuring instrument(s)
is established via available interface adapters.
Depending upon device type, one or several of the following
operating modes are possible:
• Device Parameters Configuration
Remote configuration and querying of device-specific func-
tions and parameters, for example measuring function, mea-
suring range and memory parameters. Frequently used device
settings can be saved to configuration files for easy recall.
• Online Recording of Measurement Data
Read-in, display and recording of momentarily measured data
from the interconnected device.
– Measuring channels Up to 10
– Start recording Manual, triggered by measured value,
time triggered
– Recording mode > Time controlled with a sample
interval of
0.05 s* ... 1 s ... 60 min.
> Manually controlled
> Measured value controlled in event
of exceeded limit/delta value
– Recording duration: max. 10 million intervals
* Depending upon device type, measuring function, number of measuring channels
and communication mode (e.g. via modem), sample intervals of less than 1 second
cannot be used.
• Reading Out and Visualizing Stored Data
If supported by the device: read-in and display of offline data
recorded to device memory
For purposes of analysis, data recorded online or read in from the
device’s memory can be displayed in various formats:
System Requirements
METRAwin 10 (version 5.3.x) can be run on IBM compatible PCs with
Microsoft Windows
®
98, ME, NT 4.0, 2000, XP, Vista (32/64 bit) or 7
(32/64 bit).
Y(t) Recorder Display
for Up to 6 Channels
XY Recorder Display
for Up to 4 Channels
Multimeter Display
for Up to 4 Channels
Tabular Display