Reset to Factory Configuration, continued
Factory default
settings
Dranetz-BMI has set the default values for the various parameters of the Energy
Platform.
Current Probes:
TR2500/TR2500A for A, B, C; TR2510/TR2510A for D
Scale Factors:
1:1 for V and I, channels A, B, C, D
Circuit Type:
three phase wye
Mode of Operation:
monitor
Nominal Value:
measured V, I, frequency
Monitoring Mode:
Long Term Timed Recording
Advanced Operations:
individual limit setups
RMS Variation Limits:
10% Very Low, 90% Low, 110% High for voltage; none for
current
Journal Limit:
journalling By Time for the various parameters
Triggers:
all V triggers off
Journal Interval
Power Values:
Power Values Interval: 15 minutes
Waveform S napshot: On
Demand and Energy:
Demand Sub-Interval: 5 minutes
Sub-Intervals per Interval: 3
Harmonics Journal Interval:
15 minutes
Site Name:
Energy Platform Site
Size Increment by which Data is Saved in Card:
128 MB
Clock Type:
Analog
Date:
mm/dd/yy
Language:
varies depending on unit model
NOTE: Units shipped within North America are factory set using the English/
European language group version.
Display
Backlight Timer: 1 minute
Contrast:
70%
Password Protect:
OFF