Evaluating of Measured Values
See table, “
Display Values in Consideration of Measuring Uncertainty
”,
on page 30.
Calculation of Cable Lengths for Common Copper Conductors
If the key is activated after performance of resistance
measurement, the cable lengths corresponding to common con-
ductor cross sections are displayed.
If results vary for the two different directions of current flow, cable
length is not displayed. In this case, capacitive or inductive com-
ponents are apparently present which would distort the calcula-
tion.
This table only applies to cables made with commercially available
copper conductors and cannot be used for other materials (e.g.
aluminum)!