User manual
GMC-I Messtechnik GmbH 19
6.7.1 Absorption Index (DAR) – DC Charging Test
The absorption index test is part of the polarization index test.
Insulation resistance measurements are placed in relationship to
one another after 30 and 60 seconds.
Applications:
Faster version of the polarization index test.
Set Parameters
Start Measurement
The selected polarization index menu is only displayed until the
rotary switch is activated or the parameter is changed.
7 Test Resistor for Insulation Measurement for
Checking the Insulation Measuring Instrument
According to section 5.3.1.2 of VDE 0105-100 (EN 50110-1), the
following applies: “These measuring instruments must be tested
before, and if applicable after use.”
The two outermost jacks on the connection panel must be con-
nected to each other internally via a 10 MΩ test resistor to this
end.
The sum of test resistor and cable resistance (for both cables),
including test probes, amounts to 10 MΩ ±5%. This value allows
for quick self-testing.
➭ Connect the measurement cables to the + and COM jacks.
➭ Insert the test probes into the above described jacks.
➭ Select the RiSO/iNS measuring function with the rotary
switch, as well as the desired test voltage, e.g. RiSO 100V.
➭ Press the start key and view the measurement results.
DAR
R
60s
R
30s
---------=
Polarization Index
Test voltage switch position:
50 V / 100 V / 250 V / 500 V / 1000 V
Absorption index
Insulation resistance
START
+
COM
10M
Ω
+
COMSHIELD
R
ISO
/R
INS
10 MΩ