21.4 Periodic Testing per DGUV provision 3 (previously BGV A3) 
– Limit Values for 
Electrical Systems and Operating Equipment
Limit Values per DIN VDE 0701-0702
Maximum Allowable Limit Values for Protective Conductor 
Resistance for Connector Cables with Lengths of up to 5 m 
1
This value may not exceed 1 Ω for permanently connected data processing sys-
tems (DIN VDE 0701-0702).
2
Total protective conductor resistance of max. 1 Ω
Minimum Allowable Limit Values for Insulation Resistance
* With activated heating elements (if heating power > 3.5 kW and RINS < 0.3 MΩ: 
leakage current measurement is required)
Maximum Allowable Limit Values for Leakage Current in mA 
* For devices with heating power of greater than 3.5 kW
Note 1:  Devices which are not equipped with accessible parts that are 
connected to the protective conductor, and which comply with re-
quirements for housing leakage current and, if applicable, patient 
leakage current, e.g. computer equipment with shielded power 
pack
Note 2: Permanently connected devices with protective conductor
Note 3: Portable x-ray devices with mineral insulation
Key
I
B
Housing leakage current (probe or contact current)
I
DI
Residual current
I
SL
Protective conductor current
Maximum Allowable Limit Values for Equivalent Leakage Current 
in mA 
1
For devices with heating power ≥ 3.5 kW
Test Standard Test Current
Open-Circuit 
Voltage
R
SL
Housing – 
Mains Plug
VDE 0701-0702:2008 > 200 mA 4 V < U
L
 < 24 V
0.3 Ω 
1
+ 0.1 Ω 
2
for each 
additional 7.5 m
Test 
Standard
Test 
Voltage
RINS
PC I PC II PC III Heating
VDE 0701-
0702:2008
500 V 1 MΩ 2MΩ 0.25 MΩ 0.3 MΩ *
Test Standard
I
PE
I
C
I
DI
VDE 0701-0702:2008
SC I: 3.5
1 mA/kW *
0.5
SC I: 
3.5
1 mA/
kW *
SC II: 
0.5
Test Standard I
EL
VDE 0701-0702:2008
SC I: 3.5
1 mA/kW 
1
SC II: 0.5