Instructions

58 GMC-I Messtechnik GmbH
Measurement can be aborted by pressing ON/START or ESC.
The following measured values are displayed:
RL-PE: active test resistance with upper and lower limit values
ta: response time (time during which the momentary resis-
tance is applied until the measurement is ended)
Rmin - Rmax: status display indicating momentary resistance
with reference to the number of possible resistances
–U
L1-PE: momentary voltage at the test probes between phase
conductor L1 and phase conductor PE
–UL2-PE: momentary voltage at the test probes between phase
conductor L2 and phase conductor PE
–U
L1-L2: momentary voltage at the test probes between phase
conductors L1 and L2
–I
L-PE: test current flowing through the active resistance
f: frequency of the applied voltage
Evaluation
In order to evaluate the measurement, it must be stopped. This
applies to manual as well as automatic measurement. Press the
“START” or “ESC” key to this end. The stopwatch is stopped and
the evaluation window appears.
Retrieving Saved Measured Values
The measured value cannot be saved to memory and included in
the test report until it has been evaluated (see also section 16.4).
With the help of the key shown at the right
(MW: measured value / PA: parameter), the setting
parameters can be displayed for this measurement.
OK
NOT OK