10.4 Earthing Resistance Measurement, Mains Powered – 3-Pole Measurement: 2-Pole Adapter with Probe
Key
R
B
Operational earth electrode
R
E
Earthing resistance
R
X
Earthing resistance through equipotential bonding sys-
tems
R
S
Probe resistance
PAS Equipotential bonding busbar
RE Overall earthing resistance (R
E1
//R
E2
//water pipe)
Measurement of R
E
Select Measuring Function
Select Operating Mode
Connection
2-pole adapter and probe are connected
Set Parameters
Measuring range: AUTO,
10 kΩ (4 mA), 1 kΩ (40 mA), 100 Ω (0.4 A), 10 Ω (3.7 ... 7 A)
In systems with RCCBs, resistance or test current must be se-
lected such that it is less than tripping current (½ I
ΔN
).
Connection type: 2-pole adapter + probe
Contact voltage: UL < 25 V, < 50 V, < 65 V, see section 5.7 re-
garding freely selectable voltage.
Test current waveshape:
Sinusoidal (full-wave), 15 mA sinusoidal (full-wave),
DC offset and positive half-wave
System type: TN/TT, IT
Transformer ratio: irrelevant in this case
Start Measurement