Instructions

GMC-I Messtechnik GmbH 19
Test Standard
The following must be substantiated per DIN VDE 0100 part 600:
2008:
Contact voltage occurring at nominal residual current may not
exceed the maximum allowable value for the system.
Tripping of the RCCB must occur within 400 ms (1000 ms for
selective RCDs) at nominal residual current.
Important Notes
•The PROFITEST MASTER allows for simple measurements at all
types of RCDs. Select RCD, SRCD, PRCD etc.
Measurement must be executed at one point only per RCD
(RCCB) within the connected electrical circuits. Low-resis-
tance continuity must be substantiated for the protective con-
ductor at all other connections within the electrical circuit (R
LO
or U
B
).
The measuring instruments often display a contact voltage of
0.1 V in TN systems due to low protective conductor resis-
tance.
Be aware of any bias currents within the system. These may
cause tripping of the RCDs during measurement of contact
voltage U
B
, or may result in erroneous displays for measure-
ments with rising current:
Display = I
F
- I
bias_current
Selective RCDs identified with an can be used as the sole
means of protection for automatic shutdown if they adhere to
the same shutdown conditions as non-selective RCDs (i.e.
t
a
< 400 ms). This can be substantiated by measuring shut-
down time.
Type B RCDs may not be connected in series with type A
RCDs.
Note
Bias Magnetization
Only AC measurements can be performed with the 2-
pole adapter. Suppression of RCD tripping by means of
bias magnetization with direct current is only possible via
a country-specific plug insert, e.g. SCHUKO, or the 3-
pole adapter.
Measurement With or Without Probe
Measurements can be performed with or without a probe.
Measurements with probe require that the probe and reference
earth are of like potential. This means that the probe must be
positioned outside of the potential gradient area of the earth elec-
trode (R
E
) in the RCD safety circuit.
The distance between the earth electrode and the probe should
be at least 20 m.
The probe is connected with a 4 mm contact protected plug.
In most cases this measurement is performed without probe.
Attention!
!
The probe is part of the measuring circuit and may carry
a current of up to 3.5 mA in accordance with VDE 0413.
Testing for the absence of voltage at the probe can be performed
with the U
PROBE
function (see also section 6.1 on page 16).
7.1 Measuring Contact Voltage (with reference to nominal
residual current) with
1
/
3
Nominal Residual Current and
Tripping Test with Nominal Residual Current
Select Measuring Function
Connection
Set Parameters for I
ΔN
S
I
ΔN
Nominal residual
Type 1: RCD, SRCD, PRCD etc.
Nominal current: 6 ... 125 A
Type 2: AC , A/F , B/B+ *
EV/MI
* Type B/B+/EV/MI = AC/DC sensitive
current:
10 ... 500 mA
Phase displacement: 0°/180°
X times tripping current:
Negative/positive half-wave
Negative/positive direct current
1, 2, 5 (I
ΔN
max. 300 mA)
Waveform:
Connection:
without/with probe
System type:
TN/TT, IT
Contact voltage:
Time to trip:
< 25 V, < 50 V, < 65 V