Datasheet
PROFITEST MTECH+, MPRO, MXTRA, SECULIFE IP
DIN VDE 0100/IEC 60364-6 Testers
16 GMC-I Messtechnik GmbH
WZ12C
Current clamp sensor for leak-
age current, selectable mea-
suring ranges: 1 mA to 15 A,
3% and 1 A to 150 A, 2%
Transformation ratios:
1 mV/mA, 1 mV/A
METRAFLEX P300
Flexible current clamp sensor for selective earthing resistance measurement
3/30/300 A, 1 V/100 mV/10 mV/A
Earthing Resistance Measurement Accessories
PRO-RE/2 Clamp Adapter
Adapter which is
mounted to the test
plug allowing for con-
nection of the E-Clip 2
generator clamp for 2-
clamp or ground-loop
earthing resistance
measurement.
2-clamp or ground loop
measurement is thus
made possible.
PRO-RE Adapter
Earth electrodes, auxil-
iary earth electrodes,
probe and auxiliary
probe are connected to
the tester via the
banana plug sockets,
and thus via the
adapter which is
mounted to the test
plug.
E-Clip 2 Clamp Generator
Measuring range:
0.2 A to 1200 A
Measuring category:
600 V CAT III
Max. cable dia.: 52 mm
Transformation ratio:
1000 A/1A
Frequency range:
40 Hz to 5 kHz
Output signal: 0.2 mA to 1.2 A
Equipped with laboratory safety plug inputs
Z3512A
AC Current
Sensor Clamp
Switchable measuring ranges:
1 mA to 1/100/1000 A~
Transformation ratios:
1 V/A, 100mV/A, 10 mV/A, 1 mV/A
TR25 Reel
TR50 Drum with 50m Measurement Cable
50 m measurement cable
coiled onto a plastic drum.
Connection to the inside end
of the cable is made possible
with a socket integrated into
the drum. The other end is
equipped with a banana plug.
The drum axle with handle can
be removed for space saving
storage.
Cable resistance can be com-
pensated for with the rotary
selector switch in the R
LO
position.
SP350 Earth Drill