Data Sheet
PROFITEST MTECH+, MPRO, MXTRA, SECULIFE IP
DIN VDE 0100/IEC 60364-6 Testers
12 GMC-I Messtechnik GmbH
Special Functions PROFITEST MXTRA
Test Sequences for Report Generation of Fault Simulations on PRCDs type S and K
with
PROFITEST PRCD (PROFITEST MXTRA only
):
• Three test sequences are preconfigured:
– PRCD-S (single phase/3-pole)
– PRCD-K (single phase/3-pole)
– PRCD-S (three-phase/5-pole)
• The test instrument guides you through all test steps in a
semi-automatic fashion:
Single phase PRCDs: PRCD-S: 11 test steps
PRCD-K: 4 test steps
3-phase PRCDs: PRCD-S: 18 test steps
• Each test step is assessed and evaluated by the user
(OK/not OK) for subsequent report generation purposes.
• Measurement of protective conductor resistance of the PRCD
by means of function R
LO
at the test instrument.
• Measurement of insulation resistance of the PRCD by means
of function R
ISO
at the test instrument.
• Trip test with nominal fault current by means of function I
F
at the test instrument.
• Measurement of tripping time by means of function I
ΔN
at the
test instrument.
• Varistor test with PRCD-K: measurement via ISO ramp.
Further information is included in the data sheet for the PROFITEST PRCD.
Selecting the PRCD under Test
Example Simulation Interruption
Special Functions (all Types)
Automatic Test Sequence Function
If the same order of tests with
subsequent report generation is
to be performed repeatedly, as is,
for example, specified by certain
standards, we recommend using
test sequences.
With the help of test sequences it
is possible to compile automatic
test procedures on the basis of
the manual individual measure-
ments. A test sequence consists
of up to 200 individual test steps
which have to be processed one
after the other.
The test sequences are created at a PC by means of the ETC
software and are then transferred to the PROFITEST MPRO or PROF-
ITEST MXTRA test instruments.
The measurement parameters are also configured at a PC. How-
ever, they can still be modified at the test instrument during the
test procedure before the respective measurement is launched.
Bluetooth
®
Interface (PROFITEST MTECH+/MXTRA/SECULIFE IP only)
If your PC is equipped with a Bluetooth
®
interface, wireless com-
munication is possible between the test instrument and ETC user
software for the transfer of data and test structures.
Furthermore, it is possible to connect a Bluetooth keyboard (Logi-
tech).