Manual
Table Of Contents
- 1 Safety Instructions
- 2 Applications
- 3 Documentation
- 4 Getting Started
- 5 The Instrument
- 6 Operating and Display Elements
- 7 Operation
- 8 Instrument Settings
- 9 Database
- 10 General Information on Measurements
- 10.1 Using Cable Sets and Test Probes
- 10.2 Test Plug – Changing Inserts
- 10.3 Connecting the Instrument
- 10.4 Automatic Settings, Monitoring and Shutdown
- 10.5 Measured Value Display and Memory
- 10.6 Help Function
- 10.7 Setting Parameters or Limit Values using RCD Measurement as an Example
- 10.8 Freely Selectable Parameter Settings or Limit Values
- 10.9 2-Pole Measurement with Rapid or Semiautomatic Polarity Reversal
- 11 Measuring Voltage and Frequency
- 12 Testing RCDs
- 12.1 Measuring Touch Voltage (with reference to nominal residual current) with ⅓ Nominal Residual Current and Tripping Test with Nominal Residual Current
- 12.2 Special Tests for Systems and RCDs
- 12.2.1 Testing Systems and RCCBs with Rising Residual Current (AC) for Type AC, A/F, B/B+ and EV/MI RCDs (PROFITEST MTECH+, PROFITEST MXTRA only)
- 12.2.2 Testing Systems and RCCBs with Rising Residual Current (AC) for Type B/B+ and EV/MI RCDs (PROFITEST MTECH+PROFITEST MXTRA)
- 12.2.3 Testing RCCBS with 5 × IDN
- 12.2.4 Testing of RCCBs which are Suitable for Pulsating DC Residual Current
- 12.3 Testing of Special RCDs
- 12.4 Testing Residual Current Circuit Breakers in TN-S Systems
- 12.5 Testing of RCD Protection in IT Systems with High Cable Capacitance (e.g. In Norway)
- 12.6 Testing of 6 mA Residual Current Devices RDC-DD/RCMB (RDC-DD: PROFITEST MXTRA and PROFITEST MTECH+ only)
- 13 Testing of Breaking Requirements for Overcurrent Protective Devices, Measurement of Loop Impedance and Determination of Short-Circuit Current (ZL-PE and ISC Functions)
- 14 Measuring Supply Impedance (ZL-N Function)
- 15 Earthing Resistance Measurement (Function RE)
- 15.1 Earthing Resistance Measurement – Mains Powered
- 15.2 Earthing Resistance Measurement – Battery Powered, “Battery Mode” (PROFITEST MPRO & PROFITEST MXTRA only)
- 15.3 Earthing Resistance, Mains Powered – 2-Pole Measurement with 2-Pole Adapter or Country-Specific Plug (Schuko) without Probe
- 15.4 Earthing Resistance Measurement. Mains Powered – 3-Pole Measurement: 2-Pole Adapter with Probe
- 15.5 Earthing Resistance Measurement, Mains Powered – Measuring Earth Electrode Potential (UE Function)
- 15.6 Earthing Resistance Measurement, Mains Powered – Selective Earthing Resistance Measurement with Current Clamp Sensor as Accessory
- 15.7 Earthing Resistance Measurement, Battery Powered, “Battery Mode” – 3-Pole (PROFITEST MPRO & PROFITEST MXTRA only)
- 15.8 Earthing Resistance Measurement, Battery Powered, “Battery Mode” – 4-Pole (PROFITEST MPRO & PROFITEST MXTRA only)
- 15.9 Earthing Resistance Measurement, Battery Powered, “Battery Mode” – Selective (4-pole) with Current Clamp Sensor and PRO-RE Measuring Adapter as Accessory (PROFITEST MPRO & PROFITEST MXTRA only)
- 15.10 Earthing Resistance Measurement, Battery Powered, “Battery Mode” – Ground Loop Measurement (with current clamp sensor and transformer, and pro-re measuring adapter as accessory) (PROFITEST MPRO & PROFITEST MXTRA only)
- 15.11 Earthing Resistance Measurement, Battery Powered, “Battery Mode” – Measurement of Soil Resistivity rE (PROFITEST MPRO & PROFITEST MXTRA only)
- 16 Measurement of Insulation Resistance
- 17 Measuring Low-Value Resistance of up to 200 W (Protective Conductor and Equipotential Bonding Conductor)
- 18 Measurement with Accessory Sensors
- 19 Special Functions – EXTRA Switch Position
- 19.1 Voltage Drop Measurement (at ZLN) – DU Function
- 19.2 Measuring the Impedance of Insulating Floors and Walls (standing surface insulation impedance) – ZST Function
- 19.3 Testing Meter Startup with Earthing Contact Plug – kWh Function
- 19.4 Leakage Current Measurement with PRO-AB Leakage Current Adapter as Accessory – IL Function (PROFITEST MXTRA only)
- 19.5 Testing Insulation Monitoring Devices – IMD Function (PROFITEST MXTRA only)
- 19.6 Residual Voltage Test – Ures Function (PROFITEST MXTRA only)
- 19.7 Intelligent Ramp – ta+ID Function (PROFITEST MXTRA only)
- 19.8 Testing Residual Current Monitors – RCM Function ( PROFITEST MXTRA only)
- 19.9 Checking the Operating Statuses of Electric Vehicles at Charging Stations per IEC 61851 ((PROFITEST MTECH+ & PROFITEST MXTRA)
- 19.10 PRCD – Test Sequences for Documenting Fault Simulations at PRCDs with the PROFITEST PRCD Adapter (PROFITEST MXTRA only)
- 20 Test Sequences (Automatic Test Sequences) – AUTO Function
- 21 Maintenance
- 22 Contact, Support and Service
- 23 CE Declaration
- 24 Disposal and Environmental Protection
- 25 Appendix
- 25.1 Tables for Determining Maximum and Minimum Display Values in Consideration of the Instrument’s Maximum Measuring and Intrinsic Uncertainties
- 25.2 At which values should/must an RCD actually be tripped? Requirements for Residual Current Devices (RCD)
- 25.3 Testing Electrical Machines per DIN EN 60 204 – Applications, Limit Values
- 25.4 Periodic Testing per DGUV V 3 (previously BGV A3) – Limit Values for Electrical Systems and Operating Equipment
- 25.5 Bibliography
- 25.6 Internet Addresses for Additional Information
Gossen Metrawatt GmbH 79
17.2 Protective Conductor Resistance Measurement with Ramp Sequence
– Measurement at PRCDs with Current-Monitored Protective Conductor using the PROFITEST PRCD Test Adapter as an
Accessory ( PROFITEST MXTRA only)
Application
Protective conductor current is monitored for certain types of
PRCDs. Direct activation or deactivation of the test current
required for protective conductor resistance measurements of at
least 200 mA results in tripping of the PRCD and thus to interrup-
tion of the protective conductor connection. Protective conductor
measurement is no longer possible in this case.
A special ramp sequence for test current activation and deactiva-
tion in combination with the PROFITEST PRCD test adapter per-
mits protective conductor resistance measurement without trip-
ping the PRCD.
Ramp Function Time Sequence
Due to the physical characteristics of the PRCD, measuring times
for this ramp function amount to several seconds.
If test current polarity is revered, additional waiting time is also
required during polarity reversal.
This is programmed into the test sequence in the “automatic
polarity reversal” operating mode.
Reverse polarity manually, e.g. from
“+pole with ramp” to “-pole
with ramp” . The test instru-
ment then detects the reversal of current
flow direction, stops measurement for the
required waiting time and simultaneously
displays a corresponding message (see
figure at right).
PRCD Tripping due to Poor Contacting
Good contact must be assured between the test probes at the 2-
pole adapter and the device under test or the sockets at the
PROFITEST PRCD test adapter during measurement. Interrup-
tions can result in considerable test current fluctuation which
causes the PRCD to trip under unfavorable conditions.
If this is the case, tripping of the PRCD is
automatically detected by the test instru-
ment and indicated by a corresponding
error message (see figure at the right). In
this case as well, the test instrument
automatically takes subsequently
required waiting time into account before
you can reactivate the PRCD and start the measurement over
again.
Connection
➭ Read the operating instructions for the PROFITEST PRCD
adapter, in particular section 4.1. It includes connection in-
structions for offset measurement and for protective conduc-
tor resistance measurement.
Selecting the Polarity Parameter
➭ Select the desired polarity parameter with ramp.
Measuring ROFFSET
➭ Perform offset measurement as described on page 77, in
order to assure that the test adapter’s connector contacts are
not included in the measurement results.
Note
The offset is only retained in memory until the polarity
parameter is changed. If measurement is performed with
manual polarity reversal (+pole or -pole), the offset mea-
surement has to be repeated in both polarities before
each measurement.
Measuring Protective Conductor Resistance
➭ Determine whether or not the PRCD is activated. If not, acti-
vate it.
➭ Perform protective conductor measurement as described in
section 17.1 above. Start the test sequence by briefly press-
ing the ON/START ▼ key. The predetermined duration of the
measuring phase can be extended by pressing and holding
the ON/START ▼ key.
Start Measurement
The symbol shown at the right appears during the mag-
netization phase (rising curve) and the subsequent mea-
suring phase (constant current).
If measurement is aborted already during the rising phase, no
measurement results can be ascertained or displayed.
After measurement, the demagnetization phase (falling
curve) and subsequent waiting time are indicated by the
inverted symbol shown at the right.
No new measurements can be started during this time.
Measurement results cannot be read and measurement
with the same or another polarity cannot be started until
the symbol at the right appears.
Measuring Phase Demagnetizing
and Waiting Time
Result
Time [s]
Rising
Phase
Test Current [A]
01 3 6
0.25
Before Polarity Reversal
or
Restart
Representation of Measuring and Waiting Times for
Protective Conductor Resistance Measurement at
PRCDs with the PROFITEST MXTRA