15.9 Earthing Resistance Measurement, Battery Powered, “Battery Mode” – Selective (4-pole)
with Current Clamp Sensor and PRO-RE Measuring Adapter as Accessory (PROFITEST MPRO & PROFITEST MXTRA only)
General
When measuring earthing resistance in systems with several par-
allel connected earth electrodes, total resistance of the earthing
system is measured.
Two earth spikes (auxiliary earth electrode and probe) are set for
this measurement. Measuring current is fed between the earth
electrode and the auxiliary earth electrode and voltage drop is
measured between the earth electrode and the probe.
The current clamp is positioned around the earth electrode to be
measured, and thus only that portion of the measuring current
which flows through the earth electrode is measured.
Connection
Position the spikes
for the probe and the auxiliary electrode at least 20, respec-
tively 40 meters from the electrode (see figure above).
Make sure that no excessively high contact resistances occur
between the probe and the ground.
Attach the PRO-RE adapter (Z501S) to the test plug.
Connect the probes, the auxiliary electrode and the electrode
via the 4 mm banana plug sockets at the PRO-RE adapter.
In doing so, observe labeling on the banana plug sockets.
Connect the Z3512A current clamp sensor to jacks (15) and
(16) at the test instrument.
Attach the current clamp sensor to the earth electrode.
Select Measuring Function
Select Operating Mode
The selected operating mode is displayed inversely:
white battery icon against black background.
Set Parameters at Tester
Measuring range: 200
Note
After switching to selective measurement, the AUTO mea-
suring range is activated automatically if a measuring
range of greater than 200 had been selected.
Connection type: selective
Current clamp sensor transformer ratio:
1:1 (1 V/A,) 1:10 (100 mV/A), 1:100 (10 mV/A)
Distance d (for measuring
E
): irrelevant in this case
Set Parameters at Current Clamp Sensor
Current clamp sensor measuring range: see table below
Select Measuring Range at the Current Clamp Sensor
Important Instructions for Use of the Current Clamp Sensor
Use only the Z3512A current clamp sensor for this measure-
ment.
Use the clamp in the permanently connected state. The sen-
sor may not be moved during measurement.
The current clamp sensor may only be used at an adequate
distance from powerful extraneous fields.
Make sure that the current clamp sensor’s connector cable is
laid separate from the probe cables to the greatest possible
extent.
Start Measurement
PROFITEST MPRO /PROFITEST MXTRA
R
E
Test Instrument Z3512A Clamp
Parameters
Transformation Ratio
Switches Measuring Range
1:1
1 V / A
1 A / × 1 1A
01:10
100 mV / A
10 A / × 10 10 A
1:100
10 mV / A
100 A / × 100 100 A