13.1.1 Measurement with Positive Half-Waves (PROFITEST
MTECH+, PROFITEST MXTRA only)
Measurement by means of half-waves plus direct current makes it
possible to measure loop impedance in systems which are
equipped with RCCBs.
In the case of DC measurement with half-waves, selection can be
made between two variants:
DC-L: Reduced bias current
but faster measurement as a result
DC-H: Higher bias current providing more reliability with regard
to non-tripping of the RCD
Select Measuring Function
Set Parameters
* Parameters used for report generation and do not influence the mea-
surement
Sinusoidal (full-wave) Setting for circuit without RCD
15 mA sinusoidal Setting for motor protection switch only
with small nominal current
DC + half-wave Setting for circuit with RCD
Start Measurement
Semiautomatic
measurement
(conductor
reference change)
13.2 Evaluation of Measured Values
The maximum permissi-
ble loop impedance Z
L-
PE
which may be dis-
played after allowance
has been made for the
instrument’s maximum
measuring and intrinsic
uncertainties (under nor-
mal measuring condi-
tions) can be determined
with the help of Table 1
on page 100. Intermedi-
ate values can be inter-
polated.
The maximum permissi-
ble nominal current for
the protective device (fuse or circuit breaker) for a line voltage of
230 V after allowance has been made for maximum measuring
error can be determined with the help of Table 6 on page 101
based on measured short-circuit current (corresponds to IEC
60364-6).
Z
L-PE
2-pole
Measurement with country-specific
plug insert (e.g. Schuko)
Note
Selecting the test probe, as well
as Lx-PE reference or AUTO, is
only relevant with regard to
report generation.
Semiautomatic measurement
See also section 10.9 regard-
ing the AUTO parameter.
Polarity Selection
measurement