one of the following displays depending upon poling of the
plug:
Display at the connection pictograph:
PE interrupted (x), or underlying protec-
tive conductor bar interrupted with refer-
ence to the keys at the test plug
Cause:
Voltage measuring path interrupted
Consequence: measurement is disabled
Display at the connection pictograph:
Top protective conductor bar interrupted
with reference to the keys at the test plug
Cause: current measuring path interrupted
Result: no measured value display
See “LED Indications, Mains Connections and Potential
Differences” on page 17.
Reversal of N and PE in a system without RCCBs cannot
be detected and is not indicated by the instrument.
In a system including an RCCB, the RCCB is tripped
during touch voltage measurement without RCCB trip-
ping (automatic Z
L-N
measurement), insofar as N and PE
are reversed.
10.6 Help Function
The following information can be displayed for each switch posi-
tion and basic function after it has been selected with the rotary
selector switch:
Wiring diagram
Measuring range
Nominal range of use as well as measuring and intrinsic
uncertainties
Nominal value
Press the HELP key in order to query online help.
If several pages of help are available for the respective mea-
suring function, the HELP key must be pressed repeatedly.
Press the ESC key in order to exit online help.