Manual

Gossen Metrawatt GmbH 7
5 Technical Data (excerpt)
The complete technical data and characteristic values (display
ranges, resolution, uncertainties etc.) can be found in the com-
plete operating instructions.
Ambient Conditions
Accuracy 0 … + 40 C
Operation 5 … + 50 C
Storage 20 … + 60 C (without rechargeable
batteries)
Relative humidity Max. 75%, no condensation allowed
Elevation Max. 2000 m
Nominal Ranges of Use
Voltage U
N
120 V (108 … 132 V)
230 V (196 … 253 V)
400 V (340 … 440 V)
Frequency f
N
16
Hz (15.4 … 18 Hz)
50 Hz (49.5 … 50.5 Hz)
60 Hz (59.4 … 60.6 Hz)
200 Hz (190 … 210 Hz)
400 Hz (380 … 420 Hz)
Overall voltage range 65 550 V
Overall frequency range 15.4420Hz
Waveform Sinusoidal
Temperature range 0 C … + 40 C
Supply voltage 8 12 V
Line impedance angle Corresponds to cos =1 0,95
Probe resistance < 50 k
Overload Capacity
R
ISO
1200 V continuous
U
L-PE
, U
L-N
600 V continuous
RCD R
E
R
F
440 V continuous
Z
L-PE
, Z
L-N
550 V (Limits the number of measurements
and pause duration. If overload occurs, the
instrument is switched off by means of a
thermostatic switch.)
R
LO
Electronic protection prevents switching on
if interference voltage is present
Protection with
Fine-Wire Fuse FF 3.15 A 10 s,
Fuses blow at > 5 A
Electrical Safety
Protection class II per EN 61010-1
Nominal Voltage 230/400 V (300/500 V)
Test voltage 3.7 kV, 50 Hz
Measuring category CAT III 600 V and CAT IV 300 V
Pollution degree 2
Fuses
L and N terminals 1 fuse link ea.
FF 3.15 A/500G 6.3 x 32 mm
Mechanical Design
Dimensions W × L × D = 260 × 330 × 90 mm
Weight approx. 2.7 kg with rechargeable batteries
Type of protection Housing: IP40; test probes: IP40
per EN 60529
Data Interfaces
Type USB for PC connection
Type RS-232 for barcode and RFID readers
6 Scope of Functions
PROFITEST ...
(article number)
MBASE+
(M520S)
M
PRO
(M520N)
M
TECH+
(M522R)
M
XTRA
(M522P)
Testing of residual current devices (RCDs)
U
B
measurement without tripping the RCCB
✓✓✓✓
Tripping time measurement
✓✓✓✓
Measurement of tripping current I
F
✓✓✓✓
Selective, SRCDs, PRCDs, type G/R
✓✓✓✓
AC/DC sensitive RCDs, types B and B+
——
✓✓
Testing of insulation monitoring devices (IMDs) ——
Testing Residual Current Monitoring Devices (RCMs) ——
Testing for N-PE reversal
✓✓✓✓
Measurements of loop impedance Z
L-PE
/ Z
L-N
Fuse table for systems without RCDs
✓✓✓✓
Without tripping the RCD, fuse table ——
✓✓
15 mA measurement
1)
1)
The so-called live measurement is only advisable if there is no bias cur-
rent within the system. Only suitable for motor protection switches with
small nominal current values.
✓✓✓✓
Earth resistance R
E
(mains operation)
I/U measuring method (2/3-wire measuring method via
measuring adapter: 2-wire/2-wire + probe)
✓✓✓✓
Earthing resistance R
E
(battery operation)
3 or 4-wire measuring method via PRO-RE adapter
Soil resistivity E (battery operation)
(4-wire measuring method via PRO-RE adapter)
Selective earthing resistance R
E
(mains operation)
with 2-pole adapter, probe, earth electrode and current
clamp sensor (3-wire measuring method)
✓✓✓✓
Selective earthing resistance R
E
(battery operation)
with probe, earth electrode and current clamp sensor
(4-wire measuring method via PRO-RE adapter and current
clamp sensor)
Earth loop resistance R
ESCHL
(battery operation)
with 2 clamps (clip-on current transformer direct and clip-
on current transformer via PRO-RE/2 adapter)
Measurement of equipotential bonding R
LO
automatic polarity reversal
✓✓✓✓
Insulation resistance R
ISO
Variable or rising test voltage (ramp)
✓✓✓✓
Voltage U
L-N
/ U
L-PE
/ U
N-PE
/ f
✓✓✓✓
Special measurements
Current measurement with clamp I
L
, I
AMP
✓✓✓✓
Rotating Field Direction
✓✓✓✓
Earth leakage resistance R
E(ISO)
✓✓✓✓
Voltage drop (U)
✓✓✓✓
Standing-surface insulation Z
ST
✓✓✓✓
Meter start-up (kWh test)
✓✓✓✓
Leakage current with PRO-AB adapter (IL)
——
Residual voltage test (Ures)
——
Intelligent ramp (ta + I)
——
Electric vehicles at charging stations (IEC 61851-1)
——
✓✓
Documentation of fault simulations at PRCDs with the
PROFITEST PRCD adapter
——
Features
Selectable user interface language
2)
2)
currently available languages D, GB, I, F, E, P, NL, S, N, FIN, CZ, PL
✓✓✓✓
Memory (database for up to 50,000 objects)
✓✓✓✓
Automatic test sequences function
✓✓✓✓
RS 232 port for RFID/barcode reader
✓✓✓✓
USB port for data transmission
✓✓✓✓
PC database and report generating software ETC
✓✓✓✓
Measuring category: CAT III 600V / CAT IV 300 V
✓✓✓✓
DAkkS calibration certificate
✓✓✓✓