Datasheet

Gossen Metrawatt GmbH 19
PROFITESTMASTER SERIES
PROFITESTMTECH+, MPRO, MXTRA, MBASE+
IEC 60364-6, EN 50110-1
E-Mobility Accessories
PROFITEST EMOBILITY (M513R)
Adapter for standards-compliant testing of single and 3-phase, mode
2 and 3 charging cables with simulation of faults in accordance with
DIN EN 50678 / DIN EN 50699 and the manufacturer’s specifications
Testing of mode 2 and 3, single
and 3-phase charging cables
Function test, i.e. tripping test by
means of simulating the follow-
ing faults: interruption, reversed
wires and PE to phase
Measurement of protective con-
ductor current with current
clamp transformer as accessory
Measurement of protective con-
ductor and insulation resistance
•Tripping test with nominal resid-
ual current and measurement of
time to trip
Evaluation and documentation of individual test steps
Test Adapter for Electric Charging Points (single/3-phase, type 2)
Single and 3-phase test adapter with type 2 plug for testing the
effectiveness of protective measures at electric charging points:
METRALINE PRO-TYP EM I (Z525F)
METRA,PRO-TYP EM III (Z525H): with earthing contact
socket and interchangeable test plug
Vehicle simulation (CP):
Vehicle states A through E
are selected with a rotary
switch.
Cable simulation (PP):
The various codings for
charging cables with 13, 20,
32 and 63 A, as well as “no
cable connected”, can be
simulated with the help of a
rotary switch.
Fault simulation:
Simulation of a short-circuit
between CP and PE by
means of a rotary switch
Indication of phase voltages
via LEDs:
Depending on the charging
station, either one or three
phases can be active.
Testing of electric charging
stations with permanently
attached charging cable by
means of an extended CP
test pin
Fault Simulation Accessories
PROFSIM 1 (M560A) PROFSIM 2 (M560B)
Installation board with option for fault simulation for measure-
ments per IEC 60364-6 and EN 50110 for training and project
work.
Further information regarding accessories can be found:
In our Measuring Instruments and Testers catalog
On the Internet at www.gossenmetrawatt.com
Z525F
Z525G
Z525H
M560A
Service line with main ground-
ing busbar, external and inter-
nal lightning protection, earth
measurements, TN/TT systems
M560B
Sub-distribution branch with
installation circuits, RCD type
B, RCBO (FI/LS)