User Manual

Table Of Contents
32 GMC-I Messtechnik GmbH
11 Measurement of Insulation Resistance
Attention!
!
Insulation resistance can only be measured at voltage-
free objects.
11.1 General
Select the Measuring Function
Connection
2-pole or test plug
Note
If you use the country-specific measuring adapter, insula-
tion resistance is only measured between the phase con-
ductor terminal designated “L” and the protective con-
ductor terminal PE!
Note
Checking Measurement Cables Before Measurements
Before performing insulation measurement, the test
probes on the measurement cables should be short-cir-
cuited in order to assure that the instrument displays a
value of less than 1 k. In this way, incorrect connection
can be avoided and broken measurement cables can be
detected.
Set Parameters
* Freely adjustable voltage (see section 5.7)
Polarity Selection
* AUTO parameter (see section 5.8)
Breakdown Current for Ramp Function
Limit Values for Breakdown Voltage
Limit Values for Constant Test Voltage
Test voltage
A test voltage which deviates from nominal voltage, and is usually
lower, can be selected for measurements at sensitive compo-
nents, as well as systems with voltage limiting devices.
Voltage type
The “U
INS
rising test voltage function (ramp function) is used to
detect weak points in the insulation, as well as to determine
response voltage for voltage limiting components. After pressing
the
ON/START key, test voltage is continuously increased until the
specified nominal voltage U
N
is reached. U is the voltage which is
measured at the test probes during and after testing. This voltage
drops to a value of less than 10 V (see section entitled “Discharg-
ing the Device Under Test”).
Insulation measurement with rising test voltage is ended:
As soon as specified maximum test voltage U
N
is reached and
the measured value is stable
or
As soon as specified maximum test voltage is reached
(e.g. after sparkover occurs at breakdown voltage).
Specified maximum test voltage U
N
or any occurring triggering or
breakdown voltage is displayed for U
INS
.
R
INS
Voltage type: constant
Test voltage
:
50 V / 100 V / 250 V / 325 V / 500 V / 1000 V
Voltage type: rising/ramp
Earth leakage resistance:
xxx V*
2-pole measurement (selection relevant for report genera-
ting only), measurements between:
Lx-PE / N-PE / L+N-PE / Lx-N / Lx-Ly / AUTO*
where x, y = 1, 2, 3
Limit Value:
I > I
Limit
U
INS
(U
INS
)
STOP
Lower limit value:
U
INS
(U
INS
)
Enterable range:
40 to 999 V
Upper limit value:
Limit Value:
R
INS
< Limit Value
LIMIT
U
INS
(U
INS
)