Data Sheet
3-349-392-03
3/4.14
GMC-I Messtechnik GmbH
METRACLIP62
Clip-On Ammeter for the Measurement of
Leakage and Charging Current
Applications
• Measurement of leakage current at grounded conductors
• Measurement of leakage current
at single-phase or 3-phase systems
• Measurement of line current
• Measurement of charging current
Applicable Regulations and Standards
Characteristic Values
Measuring sensor Hall effect
Measuring Ranges
1)
Frequency range: 50 60 Hz, corner frequency 2 kHz
2)
additional error for hall effect due to hysteresis: 3% rdg.
Key: rdg. = measured value (reading)
Reference Conditions
Ambient temperature
+23 C 5 C
relative humidity max. 80%
IEC 61010-1/EN 61010-1/
VDE 0411-1
Safety requirements for electrical equipment for
measurement, control and laboratory use
– General requirements
EN 60529
VDE 0470 Part 1
Test instruments and test methods
Degrees of protection provided by enclosures (IP
code)
DIN EN 61326
VDE 0843 Part 20
Electrical equipment for measurement, control
and
laboratory use – EMC requirements
Meas. Range Input Resolution
Accuracy at 18 ... 28
C,
max. 80% relative
humidity
A AC TRMS with automatic zero balancing
200 mA 0 199.9 mA 100 A 1.0% rdg. 5 digits
1)
2000 mA 0 1999 mA 1 mA 1.0% rdg. 5 digits
1)
10 A 0 9.99 A 0.01 A
1.0% rdg.
10 digits
1)
A DC with automatic zero balancing
200 mA 0 199.9 mA 100 A 1.0% rdg. 3 digits
2)
2000 mA 0 1999 mA 1 mA 1.0% rdg. 3 digits
2)
10 A 0 9.99 A 0.01 A 1.0% rdg. 10 digits
2)
• 3 measuring ranges 1 mA . . . 10 A AC TRMS / DC
• High resolution due to hall effect sensor
• Switch-over between DC and AC measurements
• Zero balancing for DC measurements
• Storage of reference values for AC measurements
• Display of maximum or minimum current measured value
• Storage of measured value (DATA HOLD)
• Battery saving circuit
• Insensitive to magnetic interference fields thanks to double
shielding