User manual

14 GMC-I Messtechnik GmbH
5.2 Visual Inspection
Visual inspection is performed prior to measurements with the test instrument.
Visual inspection includes:
damage to connector cables;
insulation damage;
selection and application of conductors and plugs for their intended use;
condition of mains plug, of connection terminals and wires;
defects of bending protection;
defects of connector cable strain relief;
condition of fastenings, of conductor fixings, of the fuse holder which is accessible to the
user, etc.;
damage to the housing and protective covers;
signs of excessive strain or improper use/handling;
signs of inadmissible tampering or modifications;
fouling, corrosion or aging to a degree unduly impairing the safety of the instrument;
fouling and/or clogging of openings for cooling purposes;
condition of air filters;
leakproofness of containers for water, air or other agents/fluids, condition of pressure
control valves;
operation of switches, control and/or setting equipment, etc.;
legibility of safety labels or symbols, of rated values and position indicators.
5.3 Measuring Protective Conductor Resistance
In the case of instruments equipped with a protective conductor, connect the DUT as de-
scribed in the following picture.
here: dut (Safety class I) and mains plug, also see chapter 4.4, page 11.
Set the measuring function selector switch to the “R
SL
20 Ω” position.
Read the measured value in “Ω” from the LCD
Move the cable from the DUT during the measurement, section by section over its entire
length, in order to locate interruptions.
Protective conductor resistance may not exceed the following values:
To test socket
R
SL
To housing for measurement of protective conductor resistance