User manual
14 GMC-I Messtechnik GmbH
5.2 Visual Inspection
Visual inspection is performed prior to measurements with the test instrument.
Visual inspection includes:
• damage to connector cables;
• insulation damage;
• selection and application of conductors and plugs for their intended use;
• condition of mains plug, of connection terminals and wires;
• defects of bending protection;
• defects of connector cable strain relief;
• condition of fastenings, of conductor fixings, of the fuse holder which is accessible to the
user, etc.;
• damage to the housing and protective covers;
• signs of excessive strain or improper use/handling;
• signs of inadmissible tampering or modifications;
• fouling, corrosion or aging to a degree unduly impairing the safety of the instrument;
• fouling and/or clogging of openings for cooling purposes;
• condition of air filters;
• leakproofness of containers for water, air or other agents/fluids, condition of pressure
control valves;
• operation of switches, control and/or setting equipment, etc.;
• legibility of safety labels or symbols, of rated values and position indicators.
5.3 Measuring Protective Conductor Resistance
➭ In the case of instruments equipped with a protective conductor, connect the DUT as de-
scribed in the following picture.
here: dut (Safety class I) and mains plug, also see chapter 4.4, page 11.
➭ Set the measuring function selector switch to the “R
SL
20 Ω” position.
➭ Read the measured value in “Ω” from the LCD
➭ Move the cable from the DUT during the measurement, section by section over its entire
length, in order to locate interruptions.
Protective conductor resistance may not exceed the following values:
To test socket
R
SL
To housing for measurement of protective conductor resistance