Datasheet

Ref : BDR_UK1-8_Master-clock-Time-servers-Software-V5.1-priceless
All technical changes, aesthetic, colour can be made without notice. 1
RADIO TIMING
®
9s
RT9s master clock ensures synchronization of
clocks and computer network.
NTP Time Server.
Configuration and supervision via Ethernet
network.
Features
Automatic time setting upon mains connection according to
synchronization source .
Pre-programmed daylight saving time.
Supervision
Communication on Ethernet, easy configuration via WEB pages
(IHM user friendly).
Integrated supervision via SNMP V2.c protocol.
Security
Memorization of time information by lithium battery.
Backup configuration settings in flash memory.
Specifications
Power Supply
230 VAC/50-60Hz
115 VAC/50-60Hz
48 VDC
Certifications
CE, EN 60950 (security), EN 55022
(CEM emission), EN 55024 (CEM
immunity), ROHS
Maximal
consumption
35 VA
IP 30 IK9
MTBF 47 330 h.
MTTR
Mother board : 10 min.
Display board : 5 min.
Power board : 5 min.
Output board : 5 min.
Weight Rack 19’’ 1U : 2,5 Kg
Dimension
Rack 19’’ 1U :
482 x 44 x 266 mm (LxHxP)
Display
LCD graphics
4 lines 20 backlit characters blue
Operating
temperature
0° to 50° C
Storage temperature -20° to 80° C
Key features
Remote configuration and time setting via Ethernet.
Supervision via HTTP, SNMP, Telnet. “GT Network Manager”
Windows
® NT/XP/2000/2003/Vista(32 bits)/Windows 7.
TCXO oscillator temperature compensated quartz.
Accuracy of time base about 0.1 sec / day from 0° to 40°C.
Lithium battery : 10 years saving information, time and date.
Security of the programs provided by the flash memory storage.
Rack 19’’ 1U.
Synchronization inputs
Synchronization via :
- DCF (Europe).
- France Inter (Europe).
- GPS antenna without power supply up to 100m on a single
telephone pair (via a GPS/DCF converter).
- AFNOR NFS 87500 (IRIG B).
- NTP on Ethernet 10/100BaseT( RJ45 connector).
Synchronization outputs
AFNOR NFS 87500/IRIG B 1000Hz Time code output.
Millisecond accuracy.
(can drive up to 250 units of GORGY TIMING clocks. )
NTP : Network Time Protocol RFC 1305. Millisecond accuracy.
(can drive up to 500 units of GORGY TIMING clocks)..

Summary of content (2 pages)