User Manual

User Manual V1.0-2022-10-15
09 Parameters
25
Technical Data LX C138-10 LX C156-10
Usable Energy (kWh)* 1 138.24 156.67
Battery Module LX C9.2-10: 38.4V 9.21kWh
Number of Modules 15 17
Cell Type LFP (LiFePO4)
Cell Conguration 180S2P 204S2P
Nominal Voltage (V) 576 652.8
Operating Voltage Range (V) 504.0~639.0 571.2~724.2
Nominal Dis-/Charge Current (A)
*2
100
Nominal Power (kW)
*2
57.60 65.28
Short-Circuit Current 4.2kA 0.57ms@639V.dc 4.3kA 0.53ms@724.2V.dc
Operating Temperature (℃) Charge: 0 ~ +45 / Discharge: -20 ~ +50
Relative Humidity(%) 0~95%
Max. Operating Altitude (m) 2000
Communication CAN+RS485
Weight (Kg) 1480 1650
Dimensions (W×H×D) (mm) 1155×2065×730
Ingress Protection Rating IP21
Storage Temperature (℃)
0~+35 (﹤ One Year); -20~0 or +35~+45 (﹤ Three
Months)
Mounting Method Grounded
Round-trip Eciency
*1
96.0%
Cycle Life
*3
4000
Standard
and
Certication
Safety IEC62619, IEC62040, IEC63056
EMC IEC/EN61000-6-1/2/3/4
Transportation UN38.3
*1: Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system at
beginning life. System Usable Energy may vary with dierent Inverter.
*2: Nominal Charge/Discharge and power derating will occur related to Temperature and SOC.
*3: Based on 2.5~3.65V voltage rang @25±2℃ of Cell under 0.5C/0.5C test condition and
100%DOD 80% EOL.