06 Electrical Connection
User Manual V1.0-2022-10-15
18
M8
10-12N·m
4
2
3
16
1
2
10
3
11
4
12
5
13
6
14
7
15
8
9
17
18
NOTICE
• The cross-sectional area of the power cable is 35mm
2
(AWG 2); its outer diameter is 11-
13mm; the stripping length is 20±1mm and the crimping height is 9±0.2mm. Ensure the
drawing force is more than 2500N after crimping.
• The power cable shall be normal 1000V PV cables.
• The orange power terminals are positive and the black power terminals are negative.
Step 1 Strip the conductor from the cable.
Step 2 Insert the cable into the power connector. Then use tools to crimp it.
Step 3 Tighten the rear housing of the power connector.
Step 4: Connect the power cable.
6.5 Connecting Inverter Power Cable