User Manual

06 Electrical Connection
User Manual V1.0-2022-10-15
18
M8
10-12N·m
4
2
3
16
1
2
10
3
11
4
12
5
13
6
14
7
15
8
9
17
18
NOTICE
The cross-sectional area of the power cable is 35mm
2
(AWG 2); its outer diameter is 11-
13mm; the stripping length is 20±1mm and the crimping height is 9±0.2mm. Ensure the
drawing force is more than 2500N after crimping.
The power cable shall be normal 1000V PV cables.
The orange power terminals are positive and the black power terminals are negative.
Step 1 Strip the conductor from the cable.
Step 2 Insert the cable into the power connector. Then use tools to crimp it.
Step 3 Tighten the rear housing of the power connector.
Step 4: Connect the power cable.
6.5 Connecting Inverter Power Cable