User Manual
Table Of Contents
User Manual V1.0-2022-10-15 06 Electrical Connection
15
NOTICE
• Connect the PE cable rst before electrical connection. Disconnect the PE cable at last
during dismantling the equipment.
• The PE cable should be prepared by customers.The cross-sectional area of the PE cable
conductor: 8mm
2
.
LL
06 Electrical Connection
WARNING
• Ensure all switches of PCU and its upstream switches are disconnected before any electrical
connections.
• Place the cables at least 30mm away from the heating components or heat sources, otherwise
the insulation layer of the cables may be aging or broken due to high temperature.
• Tie the cables of the same type together, and place cables of dierent types at least 30mm
apart. Do not place the cables entangled or crossed.
1
2
3
4
M5
3.5-4.5N·m
6.1 Connecting PE Cable