5.1 Installation Environment
Install the BS on a at ground with sucient bearing capacity. Increase the bearing capacity
and atness of the ground by laying the foundation, adding bearing plates, and so on.
The BS shall be installed indoor.
The optimal working temperature for the BS is 20~40℃.
The working temperature for the BS shall not exceed 50℃.
Install the equipment away from heat/cold source.
Do not install the equipment in a place where the temperature changes extremely.
Install the equipment away from strong interferences.
Keep children away from the equipment.
Do not install the equipment in places prone to accumulate water.
Do not put ammable or explosive matters near the equipment.
In the event of a re, please make sure that the carbon dioxide extinguisher or Novac1230
or FM-200 is nearby. The re cannot be put out by water or ABC dry powder extinguisher.
Fireghters are required to wear full protective clothing and self-contained breathing
apparatus.
5.2 Space Requirements
05 System Installation
300mm
600mm
600mm
600mm