MBR Technical Manual

BLOWER SPECIFICATIONS
BLOWER PERFORMANCE DATA
SPEED STATIC
MBR0800**-*
SCFM
MBR1200**-*
SCFM
MBR1600**-*
SCFM
MBR2000**-*
SCFM
0.1 1240 1500 1800 2160
0.2 1170 1460 1740 2080
0.3 1120 1360 1680 1990
0.4 1060 1280 1610 1890
0.5 980 1200 1520 1790
0.6 900 1110 1430 1690
0.1 900 1380 1540 1730
0.2 850 1320 1490 1670
0.3 790 1270 1450 1590
0.4 740 1200 1400 1520
0.5 680 1140 1350 1420
0.6 605 1040 1280 1320
0.1 650 1170 1130 1520
0.2 590 1130 1100 1450
0.3 540 1080 1070 1360
0.4 500 1020 1030 1290
0.5 430 950 990 1200
0.6 330 830 930 1090
External static is for blower @ 230 volts, it does not include coil, air filter or electric heaters.
HIGH
MEDIUM
LOW
HKR HEATER DATA
NO HEAT KIT HKR-03* HKR05-(C)' HKR-06* HKR-08(C)* HKR-10(C)*
MBR
0800AA-1AA X X X X X X
1200AA-1AA X X X X X X
1600AA-1AA X X X X X X
2000AA-1AA X X X X X X
^ = Circuit 1: Single Phase for Air Handler Motor * = Revision level that my or may not be designated
Circuit 2: 3-Phase for HKR3 Heater Kits C = Circuit Breaker option
X = Allowable combinations
~ = Restricted combinations
BLOWER
ELECTRIC HEATER KIT
HKR-15C* HKR-20C* HKR-21C* ^HKR3-15* ^HKR3-20*
MBR
0800AA-1AA ~ ~ ~ ~ ~
1200AA-1AA X X X X X
1600AA-1AA X X X X X
2000AA-1AA X X X X X
^ = Circuit 1: Single Phase for Air Handler Motor * = Revision level that my or may not be designated
Circuit 2: 3-Phase for HKR3 Heater Kits C = Circuit Breaker option
X = Allowable combinations
~ = Restricted combinations
BLOWER
ELECTRIC HEATER KIT