HTP Installation Instructions
2
REMOVE
REMOVE
GAS FURNACE
FIELD FABRICATED SUPPORT
FOR UNCASED COIL
OR
BOTTOM FLANGE DETAILS (TYP.)
X
2"
OIL-FIRED FURNACE
X
6”
FIELD FABRICATED SUPPORT
FOR HI-TEMP DRAIN PAN KIT
(CASED OR UNCASED)
COIL
SUPPORT
INSTALLATION INSTRUCTIONS
To remove drain pan from coil pan assembly:
1. Remove 4 screws holding coil assembly to drain pan.
2. Discard the 4 screws.
3. Remove the drain pan.
To install the high temperature drain pan:
4. Place the coil assembly on to the new high temperature
drain pan.
NOTE: When installing a high temperature drain pan kit
for oil-fired furnace applications be sure to fabricate a 6
inch spacer as indicated below.
5. Install the 4 screws supplied with the kit (#8 X 3/8).
X = Coil Pan Width + Insulation Thickness x 2